- INSTALLATION AND TERMINATION DETAILS
- All requirements and procedures must be reviewed with UIC
Telecommunications Engineering & Design.
- All installers must be certified by the UIC Telecommunications
Engineering & Design.
- All work and material will comply with all UIC Building Standards,
federal and state laws, municipal ordinances, codes, regulations, and
direction of inspectors appointed by proper authorities having
jurisdiction.
- If there are any violations of codes, the contractor / vendor will
correct the deficiency at no cost to the University.
- Working conditions must meet the industry standards for safety and
work procedures, and protection of property established by prevailing
rules, regulations, codes, and ordinances.
- Workmanship and neat appearance shall be as important as the
mechanical and electrical efficiency of the system.
- All cables and wires shall be placed in a proper raceway and be self
supported. Cable and equipment must be firmly anchored.
- Fasteners and supports shall be adequate to support loads with ample
safety factors.
- Information outlets shall be securely installed at a uniform height on
all walls.
- Outages shall be scheduled with the UIC Telecommunications Engineering
& Design and at the customer's convenience.
- Cable shall not be formed into a condition that causes the outside
sheath to wrinkle or exceed the recommended bend radius of the
cable.
- All work areas shall be cleared of all litter, and the litter properly
disposed of by the contractor on a daily basis.
- Any unusual water seepage in manholes, IDF or FDF's should be reported
promptly to UIC Telecommunications Engineering & Design.
- All cables, terminating blocks, and terminals will be marked to
conform to the existing UIC Telecommunications numbering
system.
- Only Northern Telecom BIX CROSS-CONNECTION terminating blocks shall be
used in the NODE, IDF, and FDF's for the termination of
cables.
- ORTRONICS ORMMAC patch panels shall be used for terminating fiber
optic cables with 3M Hot Melt ST connectors for multimode and single-mode
fibers, unless otherwise specified by UIC ACCC TED.
- Labels for the NODE, IDF, and FDF cable identification should be in
accordance with the ANSI/TIA/EIA 606 Standard.
- All designation strips shall be typed or marked with a label from a
UIC ACCC TED approved printer and should be in accordance with the
ANSI/TIA/EIA 606 Standard.
- All fiber optic cable enclosures shall be equipped with all materials
required for a complete installation.
- A Northern Telecom QTBIX16A connecting tool shall be used for all BIX
terminations.
- On patch panels and jacks using 110 blocks the proper 110 tool must be
used.
- All copper patch panels and jacks shall use BIX or 110
terminations.
- All penetrations in walls, floors, and ceilings must be sealed with
City of Chicago approved fire stopping material, installed in accordance
to manufacturer=s tested specifications.
|