- CONTRACTOR INSTALLED CROSS CONNECTIONS
- Use UIC Telecommunications supplied forms to record this
information.
- All cross-connects shall be installed per the UIC
standard.
- The contractor will supply and use a minimum of category 3 single pair
blue/white cross-connect wire for all of the following
cross-connections:
- All cross-connect routing must be cleared with the UIC ACCC
Telecommunications Assignment Desk.
- A copy of the completed routing sheets must be given to:
- UIC ACCC Telecommunications Assignment Desk.
- UIC ACCC TED.
- UIC ACCC Installation.
- The UIC Project Manager.
- Pair one and two of each voice information outlet will be
cross-connected to spare F-3 pairs in the riser cables.
- The F-3 riser cable pairs will then be cross-connected to spare F-2
campus distribution cable pairs.
- The final copper pair testing by the contractor will be from the Node
F-2 BIX terminal through cross-connections to every voice information
outlet.
- Cross-connection wire to be used by the Contractor if required must
follow the following color coding:
- Blue / white for voice circuits.
- Orange / white for data circuits.
- Green / white for emergency telephone circuits (ETS).
- Brown / white for security, entry phone and card reader circuits for
the electric shop.
- Slate / white for time clock circuits.
- Red / white for fire alarm circuits.
|