- GENERAL SPECIFICATIONS AND SUMMARY
- General
- Work includes:
- The Telecommunications Contractor is to provide a complete voice and data
information distribution system including all raceways, cabling, information
outlets, termination materials, and all terminations. This must include
coordination with the University of Illinois at Chicago Telecommunications
Engineering & Design. Locations of new telecommunication information
outlets are indicated on the electrical- telecommunications
drawings.
- The following hardware will be provided by the Electrical Contractor for
each telecommunications outlet: A standard telecommunications outlet
consisting of two jacks (one-voice, one-data), and a two hole recessed
face plate. The Electrical-Telecommunications Contractor will furnish and
install all materials unless otherwise specified, and complete all
terminations and testing.
- SUBMITTAL - Submit the following according to Conditions of the
Contract and Division 1 Specification Sections:
- Product data for system components.
- Full scale AutoCAD drawings on 3.5" disk indicating the exact layout and
location of the communications system raceways and
devices.
- QUALITY ASSURANCE
- Comply with NFPA 70, "National Electric Code" and Chicago
Electrical Code.
- Comply with the UIC Telecommunications Building Standards. Contact UIC
Telecommunications Engineering & Design at (312)996-8427 or (312)996-2354
for additional information.
- Provide materials that are listed and labeled by a "Nationally
Recognized Testing Laboratory" (NRTL).
- The terms "Listed" and "Labeled" are defined in the "National
Electrical Code," Article 100.
- Listing and Labeling Agency Qualifications are defined in OSHA Regulation
1910.7.
- Comply with FCC Regulations Part 68, Chapter 1,"US Code of Federal
Regulations," Title 47 for all telephone system and cable connection
components.
- COORDINATION OF WORK (PROJECT MANAGER)
- Coordinate the Work of this Section with the requirements of the
University of Illinois at Chicago Telecommunications Department. Insure
that the contractor has a copy of the UIC Telecommunications Building
Standards. UIC Telecommunications Engineering & Design will supply
copies upon request.
- Meet jointly with the representatives of the UIC Telecommunications
Engineering & Design and the user's coordinating representative to
exchange information and agree on details of installation
interfaces.
- Record agreements reached in meetings and distribute the record to the
other participants.
- Coordinate demolition activities with the UIC Telecommunications
Engineering & Design to minimize service disruptions and confusion over
what activities must take place.
- If any telecommunication information outlets need to be removed because
of the demolition of walls and ceilings, UIC Telecommunications Engineering
& Design must be notified two working days prior to their removal, and an
"AS" Telecommunications form is required. To expedite the removal, a phone
call to UIC TED and a fax of the "AS" will help. The number to call is
(312)996-8427 or (312)996-2354, and the fax number will be supplied at the
time of the call. A list of the outlet numbers to be removed must be supplied
on the AS form, and the form should be delivered to UIC Telecommunications
Engineering & Design. The form may be faxed, then sent by campus
mail.
- Coordination of demolition activities with the UIC Telecommunications
Engineering & Design must be strictly enforced to minimize service disruptions
and confusion over what activities must take place.
- A new drawing of the proposed floor layout must be available for use by
UIC TED.
- Prior to any remodeling or demolition, a telecommunication AS order must
be placed to remove all UIC telephone sets. If an order is not placed the
project will be billed for the cost of damaged or missing phones. All single
line analog sets (2500 style) are the property of the department and shall be
turned over to the department. All other sets are to be delivered to the
Telecommunications Stores Office, B-27 in building 963.
- UIC telecommunications outlets, cabling, terminal blocks, patch panels,
racks, or other hardware will be moved, disconnected, or removed without
prior approval of UIC TED.
- If any telecommunications outlets need to be removed for any reason, the
UIC TED must be notified at least five working days prior to their removal.
The number to be called is (312)996-8427 or (312)996-2354.
- Upon notification, UIC TED will investigate what work operations must be
done prior to the start of demolition. UIC TED will arrange for the dispatch
of a UIC Telecommunication Technician to perform the work, if necessary. The
technician will disconnect the jack cables being removed at the FDF only,
unless other arrangements have been made in advance with the UIC
TED.
- No UIC Telecommunication outlets, cabling, terminals, or other hardware
will be moved, disconnected, or removed without the prior approval of UIC
Telecommunications Engineering & Design.
- After all preliminary work is completed, the UIC Telecommunications
Engineering & Design will inform the necessary coordinator that they can
proceed. At this time the specified cable, raceways, information outlets, and
other telecommunication materials involved can be removed. The removed A and B
jacks, their plates, patch panels, BIX equipment, or any other reusable
material shall be returned to UIC TED. All other materials shall be disposed
of properly by the contractor in an accepted manner.
- The contractor shall provide updated drawings to UIC Telecommunication
Engineering & Design indicating the as-built condition. These drawings will
be used to update all UIC records and drawings.
- The UIC Telecommunication Engineering & Design is responsible for the
permanent numbering assignment of the telecommunications outlets. The
technician pulling the cables shall clearly mark each cable at both ends with
the correct outlet number. Each telecommunication outlet will have one
identification number, which will be the same as the assigned outlet number.
- CERTIFICATION OF INSTALLERS
- The contractor will install a complete raceway system, pull the cables,
mount the hardware, and terminate the cables at both ends. They must have
QUALIFIED INSTALLERS THAT ARE CERTIFIED BY UIC TELECOMMUNICATIONS ENGINEERING
& DESIGN TO INSTALL RACEWAYS, PULL CATEGORY 5 AND OTHER COMMUNICATION
CABLES (BOTH COPPER AND FIBER), INSTALL ALL RACKS, PATCH PANELS, COMMUNICATION
CABINETS, BIX BLOCKS, TELECOMMUNICATION INFORMATION OUTLETS, AND ALL RELATED
MATERIALS, DO ALL TERMINATIONS, AND DO ALL REQUIRED TESTING.
- Level 1 certified installers are "A" card installers that meet the
minimum requirements set forth in the certification section. They are
certified to install all raceways and mount equipment only. They may NOT pull
cable, either copper or fiber.
- Level III certified installers may pull the cable, installers may be
certified at more than one level.
- Level 2 installers are "A" or "C" card certified installers that meet
the minimum requirements set forth in the certification attachment at the
end of this document. They are certified to install certain raceways, mount
equipment, pull all cables (copper, fiber, coax, and any other data cables),
make all copper terminations, perform the copper required testing, and
must supply the required documentation of the work performed.
- An installer must be certified Level IV to terminate fiber optic
cable.
- An installer must be certified Level V to test fiber optic
cable.
- On all jobs/projects if the contractor does not have qualified installers,
then the contractor will hire another contractor that has certified installers
to complete the installation. All work performed must conform to the UIC
Telecommunications Building Standards. A list of contractors that have
certified installers may be obtained from UIC Telecommunications Engineering
& Design at (312)996-8427 or (312)996-2354.
- CABLE AND WIRING COMPONENTS
- All Telecommunications Information Outlets shall consist of the following
minimums:
- One category five white voice jack with a grey four pair category five
cable to the FDF.
- One category five black data jack with a blue four pair category five
cable to the FDF.
- One ivory two hole recessed face plate
- When a fiber optic jack is needed we will change to Ortronic jacks and the
Fib-or-Cop plate. See table below for part numbers. The information outlet
will consist of two "innie" jacks (voice not keyed and data keyed with color
coded icon tabs) and a duplex ST adapter at the bottom.
- Fib-or-Cop Jack Assembly and Components:
| ITEM |
MANUFACTURER |
PART NUMBER |
| Series II
Fib-or-Cop |
Ortronics |
|
| Duplex ST Adapter |
Ortronics |
OR-20500047 |
| Series II - 1 Jack -
"innie" module not keyed - wired 568A (for voice) |
Ortronics |
OR-60950109 |
| Series II - 1 Jack -
"innie" module keyed - wired 568A (for data) |
Ortronics |
OR-60950115 |
| White Color Coded Voice
Tab |
Ortronics |
|
| Black Color Coded Data
Tab |
Ortronics |
OR-40300200 |
- Jack Assemblies and Wall Plates:
| ITEM |
COLOR |
HUBBELL |
| Voice Jack |
White |
5110815K/WHITE |
| Data Jack |
Black |
5110815K/BLACK |
| Face Plate (2-hole) |
Ivory |
BR770WF2VD |
| Face Plate (3-hole) |
Ivory |
BR770WF3VD1D2 |
| Wall Face Plate (Wall
Phone) |
Ivory |
BR630DWP |
- The contractor shall provide the listed four pair category five and two
strand multimode fiber optic cable from the table below. Substitutions are
only allowed when advance approval, in writing, has been obtained from the UIC
Telecommunications Engineering & Design. All cable must be placed in an
approved raceway. The four pair cables for each jack will be placed by the
contractor from the telecommunications outlet to the floor distribution frame
designated by the UIC Telecommunication Engineering & Design. The amount
of cable left for termination purposes at the communications outlet shall be
12 to 18 inches, and at the FDF it shall be equal to the sum of the length,
width, and twice the height of the FDF room. In the case of a wall mounted
communications cabinet it shall be twice the sum of the height and width (of
all cabinets mounted together). Cables shall be terminated at both ends with
a maximum of three inch jacket removal and individual pairs untwisted a
maximum of one half inch.
- Category five and fiber optic interconnect cables:
| CABLE TYPE |
MOHAWK |
BELDEN |
COMMSCOPE |
COLOR |
| Voice |
M54568RB |
1583A |
|
Gray Jacket ONLY |
| Data |
M55436RB |
1583A |
|
Blue Jacket ONLY |
| 2MM Fiber |
M95222 |
|
E148998 |
Orange Jacket
ONLY |
- Cable trays must comply with the UIC Telecommunications Building Standards
"Raceways", and the following requirements:
- All cable trays must be approved by the UIC Telecommunications Engineering
& Design.
- All cable trays must be of solid bottom and side
construction.
- Cable trays for horizontal distribution cables, utilizing the trapeze
hanger method to support the cable trays, will utilize threaded rods of no
less than three eights inch diameter.
- Cable trays shall be sized for three four pair category five cables per
square inch with a minimum growth of fifty percent. Two fiber MM fiber optic
round interconnect cable shall count the same as one four pair category five
cable.
- A minimum of six inches of space above and eight inches at each side must
be left clear around the cable tray for accessability.
- Cable tray shall be located in an accessible false ceiling so that it is
readily accessible. The top of the cable tray shall not be more than twenty
four inches (24") above the dropped ceiling height.
- Conduits shall not be run parallel with the cable tray within the spaces
outlined above or between the dropped ceiling and the space outlined above.
This cable tray MUST be accessible after construction is completed!
- Raceways shall comply with the UIC Building Standards "Raceways", UIC
Telecommunications Building Standards "Raceways" and the following
requirements:
- All information system cabling shall be contained in a UIC
Telecommunications Engineering & Design approved continuous metal raceway
system.
- All building conduits shall be metallic and run in the most practical
direct route.
- All conduit runs for informational outlets shall be a minimum of one
inch trade size, and shall not exceed 295' total terminated cable length.
All conduits shall be equipped with a plastic or nylon pull line that is
rated at least 200 lbs. test.
- Conduit sections shall be no longer than 90'. Conduit runs longer than
90' will require a pull box at 90' maximum intervals.
- Conduit runs containing more than two ninety degree bends shall require a
pull box. All offsets shall be rated as equivalent to a ninety degree bend.
- Conduit bends shall be a standard of ten times the outside diameter of the
conduit unless otherwise approved by the UIC Telecommunications Engineering
Department.
- Conduits entering Floor Distribution Frame (FDF) spaces from station
outlets shall penetrate the closet walls at a height above the plywood panels,
cable tray, or ladder rack. They shall extend into the room far enough to
install insulated grounding bushings and be bonded to ground. In no case shall
they extend into the room more than four inches.
- After installation, all conduits shall be:
- Clean, dry, and unobstructed.
- Capped for protection if empty.
- Labeled for identification.
- Allowable fill capacity for four pair category five cables and four pair
category five cables in combination with two fiber MM fiber optic round
interconnect cables will be in accordance with the UIC Telecommunications
Building Standard indicated below, based on conduit lengths and number of
bends.
- Conduit fill chart
| Conduit
Size |
0.75" |
1.00" |
1.25" |
1.50" |
2.00" |
| Max. Number of
Cables |
3 |
5 |
9 |
12 |
22 |
| Conduit
Size |
2.50" |
3.00" |
3.50" |
4.00" |
| Max. Number of
Cables |
34 |
49 |
67 |
88 |
- Wiremold fill chart
| Wiremold size &
configuration |
2100 |
3000 |
4000 w/o dividerw/o
outlet |
4000 w/o dividerwith
outlet |
4000 with divider w/o
outlet |
| Max. Number of
Cables |
4 |
16 |
33 |
26 |
16 |
| Wiremold size &
configuration |
4000 with divider with
outlet |
6000 w/o divider w/o
outlet |
6000 w/o divider with
outlet |
6000 with divider w/o
outlet |
6000 with divider with
outlet |
Max. Number of
Cables |
10 |
70 |
63 |
35 |
28 |
- Wiremold smaller than 2100 must not be installed.
- No wiremold fitting may be installed that does not insure compliance with
the minimum bend radius of category five four pair cable.
- No conduit fittings (unilets, jakes, etc.) may be installed that does not
insure compliance with the minimum bend radius of category five four pair
cable.
- Conduit runs for horizontal distribution cables, utilizing the trapeze
hanger method to support the conduits, shall utilize threaded rods of no less
than 3/8" diameter.
- Conduits that are stubbed from walls to access cable trays shall be
installed so as to meet the tray and be properly bonded to the
tray.
- Raceways shall be supported on approved types of wall brackets or trapeze
hangers. Plumbers perforated straps are not permitted as a means of support.
- Brackets or Hangers shall be manufactured by Kindorf, Unistrut, B-Line, or
other UIC Telecommunications Engineering Department approved
supports.
- Raceways and equipment shall be independently supported. Do not suspend
from water, steam, or other piping or duct work.
- Secure all supporting methods by the following means:
- Toggle bolts in hollow masonry and drywall.
- Expansion bolts in concrete.
- Wood screws, pan head sheet-metal screws or lag bolts in
wood.
- Machine screws or bolts in metal surfaces.
- Plastic anchors and pan head sheet-metal screws in drywall and plaster
walls.
- Use of powder actuated tools is prohibited.
- Where outlets are installed in steel stud type systems, provide additional
cross bracing and/or straps to make the outlets completely rigid prior to the
application of the wall facing material.
- Conduit and cable tray support systems shall be securely and adequately
installed to eliminate movement of conduit and cable tray during pulling
operations.
- Any wall extending from floor, past dropped ceiling to top ceiling, and
is penetrated by Telecommunications conduit shall be properly fire stopped.
- Boxes and Cabinets shall comply with UIC Building Standards Division 16
Section 7.03 "Pull Boxes and Splice Boxes",
Telecommunications Building Standards 7.3, and the requirements listed below:
- All pull boxes shall be placed in a straight section of conduit. Do not
use boxes in lieu of a bend.
- Align the corresponding conduits, at each end of the box, with each other
to insure that the cables are pulled straight through.
- A hinged access panel shall be provided in the ceiling directly below all
pull boxes in non-accessible ceilings. The access panel shall not be smaller
than the pull box, and the minimum size shall be 18" square.
- All boxes shall be properly and adequately secured. The boxes shall not
be supported by conduits entering the box.
- Install all pull boxes in easily accessible locations.
- Support and align boxes, cabinets, raceways, fixtures, etc. in an approved
manner and as specified herein.
- If additional components and hardware are required, the contractor shall
contact UIC Telecommunications Engineering & Design for
approval.
- All hardware required can be obtained from Anixter Company, Communication
Supply Corporation (CSC), Great Northern Wire & Cable (GNWC), Graybar Electric
Company, or any other supply house.
- INSTALLATION
- GENERAL INSTALLATION
- A complete Distribution System shall be installed which must be fully
operational when telephone instruments and switching equipment are connected.
- On remodeling projects, existing telephone outlets and wiring must be
maintained fully operational until UIC Telecommunications Engineering &
Design has received an AS order form to remove all outlets and FDF locations
involved. UIC Telecommunications Engineering & Design will make
arrangements to disconnect the outlets at the FDF only. The contractor shall
remove all cable and other materials involved with the outlets being removed.
Any BIX equipment, patch panels, jacks, plates, or other equipment designated
by UIC Telecommunications Engineering & Design that is removed shall be
given to the UIC Telecommunications Stores Office.
- WIRING INSTALLATION
- UIC TED is responsible for the permanent numbering assignment of the
telecommunication information outlets. The UIC certified level 2 or 3
technician pulling the cables must clearly mark each cable, at both ends,
with the outlet identification number assigned by UIC TED. Each
telecommunications outlet shall have only one identification
number.
- If a third jack (second data jack) is required, a second data cable must
be pulled.
- Cable will be terminated at both ends with a maximum of 3" removed from
the jacket. Individual pairs can be untwisted a maximum of 1/2".
- Installation of exposed cables or cables not in an approved raceway system
anywhere in a UIC owned building is prohibited.
- The contractor must notify UIC ACCC TED 1 working day prior to starting
installation of the raceways and 3 working days prior to pulling cables, to
allow UIC TED to check the raceways.
- The contractor shall notify UIC TED 3 working days prior to starting
terminations, and the installers are to notify UIC TED when they are on site
to start the terminations.
- Installation of all cables must be by UIC certified level 2 or 3
installers without damaging conductors or jacket. Do not bend the cable to a
radius smaller than four times the diameter of the cable. Do not exceed
manufacturer's recommended pulling tensions. Pull cables simultaneously
where more than one is being installed in the same raceway or at the same
location. Use pulling compound or lubricant where necessary. Compound used
must not damage conductor or insulation. Use pulling methods that will not
damage cable or raceway, such as fish tape, cable, rope, and wire-cable
grips.
- All cabling must be installed in approved raceways . Whenever
possible conceal raceways except in unfinished spaces and as directed by
the UIC Telecommunications Engineering & Design.
- Installation of exposed cables or cables not in an approved raceway
system anywhere in a UIC owned building is prohibited.
- In IDF's and FDF's, conductors are to be installed parallel to and at
right angles to walls. Loosely bundle and train the conductors to terminal
points with minimal excess, maintaining the proper bend radius for the cables
involved. Use wire distribution D-rings to insure a neat installation.
Whenever cable ties are necessary with category five or fiber optic cables,
only Velcro style ties shall be used. All cables shall be properly terminated.
All labeling information will be designated by the UIC Telecommunications
Engineering & Design and the contractor will be responsible for all labeling,
including telecommunications outlets, cables, blocks, and patch panels.
ANSI/TIA/EIA 606 shall be followed as specified by UIC Telecommunications
Engineering & Design.
- Terminate all conductors of cables on terminal blocks and patch panels
using tools recommended by the manufacturer and acceptable to the UIC
Telecommunications Engineering & Design.
- GROUNDING
- Install the TMGB in the IDF according to the ANSI/TIA/EIA 607 standard.
- Install a TGB in each FDF according to the ANSI/TIA/EIA 607
standard.
- All conduit, cable tray, racks, supports, cabinets, and equipment shall be
properly grounded in accordance with the ANSI/TIA/EIA 607 standard, the latest
edition of the National Electrical Code, and all other applicable codes and
regulations.
- Provide all bonding conductors (which shall be a minimum #6 AWG green
insulated stranded copper cable ), lugs, grounding bushings, clamps, etc.,
required for a complete grounding system.
- All grounding and bonding conductors shall be routed in the shortest, most
direct path.
- Absolutely NO splices shall be allowed in bonding or grounding conductors.
- The minimum bend radius of grounding and bonding conductors shall be
eight inches (8").
- UIC Telecommunications Building Standards Bonding & Grounding, shall be
strictly followed.
- IDENTIFICATION - The contractor shall identify and label all
telecommunications information outlets, cabinets, patch panels, cables, and
any other equipment necessary. These labels shall be in accordance with the
UIC Telecommunications Building Standards.
- FIELD QUALITY CONTROL
- Provide at least 3 working days notice in writing when the system is ready
for final acceptance testing to the UIC Telecommunications Engineering &
Design.
- Acceptance Tests:
- All voice jacks shall be tested, before cross connects are installed, with
the same cable analyzer as the data jacks; however, these jacks only need to
pass category three. The actual tests must be transferred to a computer and
copied to 3.5" disks. These disks are to be given to the UIC Telecommunications
Engineering Department. After the cross connects are installed the two pairs,
pins 1 and 2, must be tested from the jack to the Node for continuity and
polarity.
- All data jacks must be tested with a dual remote category five cable
analyzer. As of July 1997, the UIC Telecommunications Engineering & Design
will accept testing using the Scope 155 cable analyzers with the dual remote.
The use of any other cable analyzer must be accepted by the UIC
Telecommunications Engineering & Design, in writing, before their use will be
accepted. The actual tests must be transferred to a computer and copied to 3.5"
disks. All data jacks must pass category five requirements. These disks are
to be given to the UIC Telecommunications Engineering &
Design.
- All fiber optic cables must pass the following tests:
- For every multimode fiber installed, end-to-end attenuation loss testing
shall be performed at both 850 nm and 1300 nm wavelengths. The results must
be recorded on 3.5" disks. OTDR tests need to be taken only at one wavelength,
and they are also to be recorded to 3.5" disks.
- For every single-mode fiber installed, end-to-end attenuation loss testing
shall be performed at both 1310 and 1550 nm wavelengths. The results must be
recorded on 3.5" disks. OTDR tests need to be taken only at one wavelength,
and they are also to be recorded to 3.5" disks. If the fiber is to be left
unterminated, OTDR testing only is required. The use of a bare fiber connector
is required for this test. UIC Telecommunications Engineering & Design will
provide one if necessary.
- After all deficiencies, indicated by tests, have been corrected,
completely retest all cables affected by the deficiencies. Verify
that the total system meets all specifications and complies with all
applicable standards.
|