 |
BUILDING STANDARDS

DIVISION 14 -- CONVEYING EQUIPMENT
14 10 00 DUMBWAITERS
- Refer to applicable codes for rated construction requirements.
- Matot is the preferred manufacturer.
14 21 00 ELECTRIC TRACTION ELEVATORS
- Scope
- General: These
standards are intended to cover the installation of
(number of elevators) passenger elevators in a first-class manner.
- Work: The work
shall include, but not be limited to, complete control
systems, controller assemblies, machine assemblies, door operation
systems, door protection systems, car assemblies and signal systems on
Elevators # (elevator numbers).
- Location: The
work shall be performed at the University of Illinois at
Chicago, Building (building number), (building legal address), Chicago,
Illinois.
- Work Included:
- General:
Contractor shall include all work necessary to complete the elevator
installation per the Contract Documents.
- Code Compliance:
Contractor shall provide any additional material or
modifications to equipment required to meet applicable Codes, Standards
and Laws.
- First-class
Condition: Contractor shall include servicing, lubrication
and painting of equipment to insure all equipment is in first-class
condition at the completion of the project.
- Multiple Parts:
Contractor shall provide the proper number of devices
or parts required. In all cases where a device or a part of the
equipment is herein referred to in the singular, it is intended to
apply to the number of devices or parts required to complete the
installation.
- Work Not Included:
- General:
Contractor shall coordinate the work identified with the other
contractors.
- Machine Room
Requirements:
- Enclosure:
Fire-rated walls shall be provided to isolate elevator equipment from
other equipment.
- Access:
Fire-rated door shall be provided which is self-closing and
self-locking. Permanent noncombustible stairs with handrails shall be
provided where floor levels for access are different.
- Cooling: Air
conditioning shall be provided to prevent room from
exceeding the maximum equipment operating temperature requirements.
- Heating: Heater
shall be provided to prevent room from falling below the minimum
equipment operating temperature requirements.
- Painting: Walls
in machine rooms shall be painted.
- Fire
Extinguisher: An ABC fire extinguisher shall be provided in each
machine room area.
- Hoist-way
Requirements:
- Enclosure:
Fire-rated wall shall be provided. Front wall shall be constructed
after entrance frames have been installed.
- Alignment:
Hoist-way shall be provided which is plumb within 1 inch.
- Projections:
Beveled guards shall be provided where the side or rear wall projects,
recedes or is set back more than 2 inches.
- Cutting: Walls
shall be cut for fixtures.
- Patching: Walls
shall be patched for fixtures. Walls shall be patched for drywall-type
entrance assemblies.
- Grouting: Walls
shall be grouted for concrete-type entrance assemblies. Floors shall be
grouted for sills.
- Painting: Walls
around entrances and fixtures shall be painted.
- Venting: Venting
shall be provided to prevent accumulation of smoke and gases as
required.
- Pit Access:
Ladders shall be provided in pits.
- Electrical
Requirements:
- Mainline
Disconnects: One lockable, fused three-phase mainline
disconnect shall be provided for each elevator in the machine room.
- Cab Lighting
Disconnect: One fused single-phase service with switch shall be
provided for each elevator in the machine room.
- Machine Room
Lighting: Adequate lighting (minimum 10 ftc) shall be
provided in the machine room. One light switch shall be provided on the
lock-jamb side adjacent to each machine room access door. Two duplex
outlets shall be provided in the machine room.
- Pit Lighting:
Adequate lighting (minimum 5 ftc) shall be provided in
the pit area. At least one covered light fixture shall be provided for
each elevator. One light switch accessible from the pit entry for each
elevator and duplex outlet shall be provided in each pit area.
- Standby Power:
Adequate power to operate one elevator in each group
shall be provided from the standby generator. Means for absorbing
regenerate power shall be provided.
- Standby Power
Signals: Two signals shall be provided to each elevator
operational control system. One signal shall activate when the power
has transferred to the standby power source. The other signal shall
activate prior to transfer back to normal power. This pre-transfer
signal shall be adjustable and initially set at 30 seconds.
- Conduit:
Conduit shall be provided from elevator hoist-ways to Fire Control
Panel.
- Cab
Requirements:
- Flooring: Tile
shall be provided for each elevator cab.
- Communication
Requirements:
- Telephone
Service: Specify the electrical contractor to provide ¾ inch
conduit, from the nearest telephone closet (FDF), 4 pair CAT 5
telephone cable and a "D-MARK" junction box near the controller of each
elevator for the purpose of providing ADA compliant telephone service
in each cab. Final trimming, testing and programming shall be performed
by University Telecommunication Department.
- Emergency
Telephone Device: Standard University Emergency Telephone
Unit (ETU), hands free, ADA compliant, will be provided by the
University. Elevator contractor shall make necessary cut out, and
provide mounting flanges with 4 tapped holes, so that the unit could be
secured flush to either the front return/entrance swing column unless
shown otherwise on drawings. The University will loan a prototype of
the ETU to the elevator manufacturer contractor for making proper cut
outs and mounting reinforcement mechanism.
- Quality Assurance:
- Qualified
Bidders: Contractor shall submit the following certified information
with the bid:
- Contractor
is currently engaged in the manufacturing and installation of elevator
equipment and has been for the previous twenty-five (25) years.
- Contractor shall
have technical qualifications of at least ten (10)
years installing microprocessor-based elevator equipment. Qualification
shall be based on having trained supervisory and installation personnel
and the facilities to install the elevator equipment proposed in the
Chicago area.
- Contractor shall
submit a list of installations totaling 100 elevators
where all the elevator equipment proposed for this installation has
been completed.
- Contractor shall
submit a list of five or more local (in the Chicago
area) installations where all the elevator equipment proposed for this
installation has been completed by him.
- Approved
Manufacturers: Contractor shall provide material from specified
manufacturers.
- Other
Manufacturers: Contractors may not provide material from other
manufacturers.
- Code Compliance:
- General:
Contractor shall comply with most-stringent applicable
provisions of the following Codes, Standards and Laws including
revisions and changes in effect on date of these standards.
- Elevator:
- ASME A17.1 -
Safety Code for Elevators and Escalators.
- ASME A17.2 -
Inspectors' Manual.
- ASME A17.3 -
Safety Code for Existing Elevators and Escalators.
- Electrical
- NFPA 70 -
National Electrical Code.
- Building:
- City of Chicago
Building Code
- Life Safety:
- NFPA 101 - Life
Safety Code
- City of Chicago
fire authority.
- Handicapped
Accessibility:
- Americans with
Disability Act.
- Illinois
Environmental Barriers Act.
- ANSI A-117.1
- Specifications
for Making Building and Facilities
- Accessible to,
and Usable by, the Physically
- Handicapped.
- Laws: Any other
Ordinances and Laws applicable within the governing jurisdiction.
- Schedule:
- General: The
contractor shall submit a complete schedule, including
material delivery dates, within 14 days of Award of Contract.
- Award of
Contract: Contractor shall not proceed until the contract is
signed by the Owner. Owner may provide written notification to proceed
prior to signing contract. Date of notification shall serve as the date
of Award of Contract for scheduling purposes.
- Installation
Period: The contractor shall not begin the installation until all
material for the first elevator is delivered.
- Final
Acceptance: Contractor shall continue to work at the location
until the final acceptance of the last elevator is completed.
- Pre-Installation Submittal:
- General:
Contractor shall assemble complete submittal packages within 30 days of
Award of Contractor.
- Product Data:
Contractor shall submit six (6) copies of the
manufacturer's specifications and installation instructions for each
product furnished.
- Power Data:
Contractor shall provide electrical calculations for all three-phase
and single-phase feeder requirements.
- Test Data:
Contractor shall provide certified laboratory test reports
on components as specified or required by referenced codes.
- Keying:
Contractor shall coordinate all keying with the Owner. Key
switches shall be Best unless otherwise specified, and shall have
construction cores. University at the end of Warranty period will
re-key the switches.
- Material
Samples: Contractor shall provide three (3) samples for each material
furnished.
- Initial Shop
Drawings: Contractor shall submit one (1) mylar and six
(6) copies of the layout, cab and fixture drawings for review.
- Drawing Review:
Drawing review shall not be interpreted as an
indication that submittal is correct or that work represented by
submittal complies with the Contract Documents.
- Submittal
Response: One mylar and two copies shall be returned to the
Contractor within 14 days. Submittal response is not justification for
revision of delivery or installation schedules without prior written
notification.
- Revised Shop
Drawings: Contractor shall incorporate changes and return one copy
within 7 days.
- Permits, Inspections and Reviews:
- General:
Contractor shall coordinate all inspections and reviews.
- Permits:
Contractor shall obtain and pay for permits, licenses and
inspection fees necessary to complete the elevator installation.
- Inspections.
Contractors shall make all tests required by the
referenced codes and/or inspection authorities. Contractor shall notify
inspection authorities with sufficient notice and have inspection
performed prior to reviews. Inspection delays are not justification for
revision of installation schedules without prior written notice.
- Reviews.
Contractor shall provide the personnel for acceptance reviews
and final reviews indicated in the Contract Documents. Contractor shall
provide 7 days notice to the Owner for each review.
- Post-Installation Submittal:
- General:
Contractor shall assemble complete submittal package within 30 days of
final acceptance of the final elevator.
- Final Shop
Drawings: Contractor shall provide six (6) complete sets of "AS INSTALLED" drawings. All changes shall be revised on the
manufacturer's drawings. No hand written changes will be accepted.
- Electrical
Wiring Diagrams: Contractor shall provide six (6) complete
sets of "AS INSTALLED" electrical wiring diagrams (EWD's). All changes
shall be revised on the manufacturer's drawings. No hand written
changes will be accepted.
- Maintenance
Manuals: Contractor shall provide six (6) copies of neatly
bound manuals including instructions explaining all operating features,
parts lists, recommended spare parts, lubrication charts and
recommended maintenance schedule. Contractor shall also provide three
(3) separate copies of the adjustment, system overview, service tool
and troubleshooting manuals.
- Keys: Contractor
shall provide the control key of construction cores
and three (3) sets of properly tagged keys to operate all key switches
and locks upon completion of the first elevator.
- Service Tool:
Elevator Contractor shall furnish to the University two
(2) laptop PC service tool with necessary software needed for
adjusting, trouble shooting and performing safety and operational
tests. It must be emphasized that the service tool shall be used
exclusively by University elevator mechanics and it shall be used only
for the elevator(s) provided under the scope of this project. The
service tool shall be delivered to the University elevator foreman on
or before the training session described by item 12 of these standards.
All necessary updating of this tool will be performed at no cost to the
University.
- Warranty:
- Period:
Contractor shall guarantee that the materials and workmanship
of the elevator equipment installed under these standards shall be
first-class in every respect. Contractor shall make good all defects,
not due to ordinary wear and tear or improper use, which may develop
within one year after the final acceptance.
- Periodic
Examination: During the Warranty period the contractor shall
lubricate all parts, examine all components of the elevators for
conformance with specified design features such as, the door timings,
checking and replacing burnt out bulbs of signals, group operation,
speed of elevator, etc. The periodic examination will be conducted at
least for one (1) hour every month for each elevator. Prior to
performing the examination the contractor shall notify the UIC elevator
foreman at least 2 days advance of the scheduled examination date.
Failure to provide this examination will result in proportionate
extension of warranty period.
- Service:
Contractor shall provide call back warranty service at no cost
to the University, with a response time not to exceed 2 hours, as
follows:
- Maintenance
work, including 24 hour-per-day, 7 day-per-week emergency
call back repair service, shall be performed by trained employees of
the elevator contractor.
- Contractor will
maintain an accurate log of all service calls, including details of the
malfunctions and repairs performed.
- At the end of
the warranty period the service call log will be turned over to the
University Elevator Foreman.
- End of Warranty
Period Review: Contractor shall provide personnel for
one warranty review. Owner may schedule this review anytime during the
warranty period, contractor shall provide any modifications to the
elevator equipment and any adjustment necessary to meet requirements of
the Contract Documents identified during the warranty review within 30
days of notification.
- Training:
- General:
Elevator Contractor shall provide training to representatives of the
Owner as follows:
- On-Site:
Contractor shall provide two (2) 40-hour, uninterrupted
adjuster level training sessions to University elevator mechanics on
University premise. University Facilities Management will make
necessary on-campus/on-site arrangement for this training. Training
shall include detailed overview of operational control system, motion
control system, door control system, signal system, trouble shooting,
servicing and periodic maintenance required.
- General:
- Outline:
- Quantity:
(calculated number of elevators) Passenger Elevators
- Type: Geared
Overhead Traction
- Capacity:
(calculated capacity) Pounds
- Speed:
(calculated speed) FPM
- Stops: (number
of stops)
- Openings:
(number of openings)
- Floors Served:
(nomenclature of floors)
- Travel: (travel
of elevators) Feet
- Entrance Size:
3'6" Wide by 7'0" High
- Entrance Type:
Center Opening
- Pre-Engineered
Systems: The elevators provided shall be from the following
pre-engineered product lines:
- ThyssenKrupp
Elevator - TAC 50 VVVF
- KONE Inc. -
Miprom 21 VVVF
- Otis - Elevonic
411
- Design
Parameters: The elevator system shall be designed, installed and
adjusted to meet the following requirements:
- Flight Time: The
elevators shall arrive at the next typical floor with
the doors open two-thirds within (calculated flight time) seconds from
the start of door closing movement. This shall be accomplished
regardless of load on the elevator or direction of the elevator.
- Door Motion
Times: The elevators shall open its doors within
(calculated door open motion time) seconds. The elevators shall close
its doors within (calculated door close motion times) seconds or the
minimum allowed by Code, whichever is greater. Door times are measured
from the start of movement until movement is stopped.
- Floor Accuracy:
The elevators shall stop within ¼" of floor regardless
of load or direction and re-level to within ¼" during
loading/unloading.
- Speed: The
elevators shall operate within 3% of the contract speed regardless of
load or direction.
- Ride: The
elevators shall operate smoothly, with less than 15 mg
horizontal acceleration, less than 4.0 feet per second-squared vertical
acceleration and less than 8.0 feet per second-cubed vertical jerk.
- Noise: The
elevators shall operate quietly, with less than 55 dBa
within the cab with the doors closed, 60 dBa with door operation and 65
dBa within the machine room. Noise is measured with a Dranatz Sound
Meter on the C scale with the background noise less than 45 dBa.
- Noise: The
elevators shall operate quietly, with less than 55 dBa
within the cab with the doors closed, 60 dBa with door operation and 65
dBa within the machine room. Noise is measured with a Dranatz Sound
Meter on the C scale with the background noise less than 45 dBa.
- Mainline
Feeders: The elevator shall have a starting current of less
than (calculated starting current) amps and a running current of less
than (calculated running current) amps with the three-phase incoming
voltage maintained within +/- 10% of 480 Volts AC and with +/- 3% of 60
cycles.
- Mainline
Harmonics: The elevator shall add not more than 5% harmonic distortion
and shall meet the requirements of IEEE 519.
- Lighting
Feeders: The elevator shall have a lighting and fan current of
less than 20 amps with the single-phase voltage being maintained within
+/- 10 of 120 Volts AC.
- Environment:
- Temperature: The
elevator shall be capable of operating properly with
the temperature being maintained below 90 degrees Fahrenheit in all
equipment areas.
- Humidity: The
elevator shall be capable of operating properly with the
humidity being maintained below 90% non-condensing in all equipment
areas.
- Heat Emissions:
- Machine Room:
The elevator shall not produce more than (calculated equipment heat
emissions) BTU's in this area.
- Hoist-way: The
elevator shall not produce more than (calculated equipment heat
emissions) BTU's in this area.
- Control Systems:
- Operational
Control:
- Group
Orientation: Provide group operational control to operate all the
elevators in each group automatically in response to car and hall
calls. The elevators shall be assigned calls as they are registered.
The closest elevator shall be assigned a hall call based on the
estimated time of arrival (ETA). Penalties shall be given to long
established hall calls and bonuses for coincident calls. The elevator
shall stop for hall calls only in the direction of travel. The elevator
shall reverse automatically in response to a hall call in the opposite
direction of travel. The elevator shall reverse without door cycle
after hold open time has expired when there is no further demand in the
direction of travel and shall close after the additional hold open time
has expired. The elevators shall zone after the last call is answered.
There shall be one zone for each elevator in the group. The lobby zone
shall be the first zone filled.
- Firefighter's
Service Operation: Provide means to operate the elevators during an
emergency. Also provide connections for future smoke detector
activation of lobby and alternate floor automatic return.
- Inspection
Operation: Provide means to operate the elevator at reduced speed from
the top of the elevator. Activation of Inspection Operation shall
remove the elevator from service.
- Independent
Service Operation: Provide means to operate the elevator in response to
only car calls. Close doors by holding a car call until doors are
completely closed. Activation of Independent Service Operation shall
remove the elevator from service. The elevator shall park with the
doors open at the last floor served.
- Hoist-way
Access Operation: Provide means to operate elevator at the top and
bottom terminals at reduced speed with both the hoist-way doors and the
car doors open. Terminal access shall be zoned.
- Car-To-Terminal
Operation: Provide means to initiate a demand at the terminal when the
access key switch is activated. The elevator shall arrive at the
terminal without activating the hall lantern or canceling the hall
call. The elevator shall remain at the terminal for 15 to 30 seconds to
allow the elevator to be placed on inspection operation. In the event
that the elevator not be removed from service during the allotted time,
the elevator shall return to group operation.
- Load
By-pass Operation: Provide means to by-pass hall calls in the event
that the elevator is sufficiently loaded. Initial setting of the load
sensing device shall be 50% of the capacity of the elevator.
- Load
Demand Operation: Provide means to initiate a hall call demand when an
elevator becomes sufficiently loaded when responding to a hall call.
The hall call demand shall be initiated in the direction in which the
elevator was traveling and shall be initiated upon activation of the
load sensing device (while the doors are open). Initial setting of the
load sensing device shall be 40% of the capacity.
- Delayed
Operation: Provide means to remove an elevator from group operation in
the event that it is delayed and cannot respond to demands.
- Anti-Nuisance
Operation: Provide means to cancel car calls in the event that the
elevator makes three (3) consecutive stops without interruption of the
door screen.
- Programmed
Shutdown Operation: Provide means to stop the elevator at the next
floor, open the doors and remove the elevator from service. The
controller shall prevent the operation of the elevator until the
problem is manually reset. This operation shall activate by the
governor over-speed device, machine room over-temperature monitor and
reduced incoming power monitor.
- Hall
Button Failure Operation: Provide means to maintain the registration of
hall calls in the event all the elevators are removed from service for
less than 5 minutes except for firefighter's service feature. After 5
minutes, all hall calls shall be canceled and remain canceled. The
timer shall be reset every time one elevator is back in-service.
- Standby
Power Operation: Provide means to automatically return one elevator at
a time to the main floor. After the last elevator has returned to the
main floor, one elevator shall continue to operate. Provide means to
override automatic return and manually select any elevator in the group.
- Advance
Lantern Operation: Provide means to indicate direction of elevator
travel. Lantern shall light at between 6 to 8 seconds prior to door
open movement and shall stay lit until doors begin to close. Audible
signal shall sound when the lantern is lit and shall sound once for up
travel and twice for down travel.
- Back-up
Group Operation: Provide means to maintain elevator service in the
event that the group operation control system cannot assign hall call
demands.
- Motion Control:
- Automatic
Operation: Provide motion control which automatically decelerates,
levels and stops the elevator in response to a call.
- Re-Leveling
Operation: Provide means to level the elevator after the elevator has
stopped to maintain floor accuracy.
- Reduce
Power Operation: Provide a means of monitoring incoming voltage. When
improper power is detected, each elevator shall first attempt a
programmed shutdown operation. When improper power to safely operate
the elevator is detected, the elevator shall stop immediately. The
monitor shall prevent the operation of the elevator if proper power is
not available.
- Over-Travel
Limiting Operation: Provide means to prevent the operation of the
elevator when it travels beyond the leveling zone at a terminal floors.
The limits switches shall operate quietly.
- Door Control
- Automatic
Operation: Provide door control which automatically opens and closes
doors.
- Force
Limiting Operation: Provide means to limit the door pressure while
closing to a maximum of 30 pounds (measured from rest) and a maximum of
7.5 foot-pounds kinetic energy.
- Reduced
Stall Force Operation: Provide means to reduce the force exerted on the
doors during a stall condition. Door pressure shall be zero pounds
after one second.
- Reduce
Speed Closing Operation: Provide means to reduce the speed during
closing to a maximum of 2.5 foot-pounds kinetic energy. Doors shall
close at reduce speed during Firefighter's Service as required.
- Nudging
Operation: Provide means to sound audible electronic tone when doors
are held open for longer than the setting of the Nudging Timer. Doors
shall remain fully open if door screen continues to be obstructed.
Doors shall fully reopen if door screen becomes obstructed during
closing.
- Door Hold
Operation: Provide separately adjustable timers to vary the time the
doors hold open as follows:
- Car Call Timer:
The amount of time the doors shall be held in response
to a car call. Timer setting shall be between 3.0 and 6.0 seconds.
- Hall Call Timer:
The amount of time the doors shall be held open in
response to a hall call or coincident call. Timer setting shall be
between 4.0 and 8.0 seconds.
- Interrupted
Screen Timer: The amount of time the doors shall be held
open after the screen is reestablished. Timer setting shall be between
1.0 and 3.0 seconds. Timer shall be reset with each interruption of the
door screen.
- Door Reversal
Timer: The amount of time the door shall be held open
after doors are fully reopened. Timer setting shall be between 1.0 and
3.0 seconds.
- Nudging Timer:
The amount of time the doors shall be held open before
sounding an audible tone. Timer setting shall be between 20 and 30
seconds.
- Initial Timer
Settings: Timers shall be initially set to the minimum
allowed by handicapped accessibility standards within the range. Car
call and door close buttons shall have no effect on timers.
- Door
Stall Operation: Provide means to reopen doors in the event that the
doors do not close all the way within 30 seconds of closing operation.
Provide means to remove the elevator from service after the third
unsuccessful attempt.
- Controller Assemblies:
- General:
Provide material from ThyssenKrupp Elevator, KONE Inc., or Otis.
- Microprocessor:
Provide a microprocessor-base unit for operational and communication
function. Provide ThyssenKrupp - TAC 50 - VVVF model, KONE Inc. Miprom
21 VVVF model, or Otis Elvonic 411 model.
- Software:
Provide nonproprietary type.
- Service Tool:
Provide all service tools require for troubleshooting.
- Drive: Provide
solid-state VVVF control for A.C. hoist motor.
- Position
Sensing: Provide digital solid-state type with maximum ¼" per
pulse. Provide a system that does not utilize a stationary tape in the
hoist-way A LED-type position indicator shall be located in the machine
room.
- Contactors and
Relays: Provide solid-state contactor which shall be
sized to insure proper conductivity and reliable operation. Contactor
shall be Nordic or equal.
- Identifications:
Provide permanent markings for all components,
including size and type of fuses, identical to those symbols found on
the Electrical Wiring Diagrams.
- Isolation
Transformers/Filters: Provide transformers and filters to isolate noise
from the electrical system.
- Labeling:
Provide UL, CSA or ASME A.17.5 label.
- Machine Assemblies:
- General:
Provide material from ThyssenKrupp Elevator, KONE Inc. or Otis.
- Machine:
Provide worm-geared traction type with deflector sheave mounted on an
isolated bed-plate.
- Motor: Provide
A.C. type directly mounted to the machine.
- Brake: Provide
D.C. type with switch to monitor brake operation.
- Vibration Sound
Dampeners: Provide rubber type to isolate the machine from the building
structure.
- Door Operation Systems:
- General:
Provide material from ThyssenKrupp Elevator, KONE Inc. or Otis.
- Operator:
Provide high-speed, heavy-duty DC master type operator with
digital velocity and position feedback. Provide a contact on the car
door which shall prevent the operation of the elevator when the car
door is not closed.
- Header: Provide
steel type shaped to provide stiff flanges.
- Tracks: Provide
removable bar or formed steel with contours to match the hangers. Each
track shall be reversible.
- Hangers: Provide
polyurethane-type with pre-lubricated sealed bearings
which will allow vertical and lateral adjustment of the hoist-way and
car door panels. Each door panel shall have two-point suspension with
separate replaceable hangers. Upthrust shall be provided to maintain
alignment of the door panels.
- Gibs: Provide
two nylon-type per door panel. Fire stops shall be properly bent down
on hoist-way door panels.
- Interlocks:
Provide an electromechanical device which shall prevent the
operation of the elevator when the hoist-way doors are not closed and
locked.
- Restrictor:
Provide device which restricts the opening of the car doors outside the
unlocking zone.
- Closer: Provide
spirator or sash weight type which shall close the hoist-way doors from
any open position.
- Door Protection Systems:
- General:
Provide material from Janus Elevator Products, Inc.
- Door Screen:
Provide infrared pulsed type which shall initiate door reopening
operation. Provide Panaforty model.
- Controller:
Provide two-relay type which shall allow reduced speed door closing
operation. Provide Panacombi Mark II model.
- Labeling:
Provide UL or CSA label.
- Car Assemblies, Guide and Balance Systems:
- General:
Provide material from ThyssenKrupp Elevator, KONE Inc. or Otis.
- Car Frames:
Provide steel plank, crosshead and stiles. Provide new Car
Top Inspection Stations with properly covered work light and 3-wire
grounded-type outlet permanently mounted to the crosshead of each
elevator. Provide new Crosshead Data Tags permanently mounted to the
crosshead adjacent to the original data tags. Both the stations and the
data tags shall be easily accessed from the hoist-way landing.
- Platforms:
Provide steel type isolated from the car frame.
- Car Guide Rails:
Provide standard T-type steel rails with brackets for
attachment to building structure. Provide any backing or intermediate
tie brackets.
- Car Guide
Assemblies: Provide roller-type which allows front-to-back
and side-to-side adjustments of each guide. Each arm shall be spring
mounted with adjustable stops. Rollers shall operate at less than 250
rpm. Guide assemblies shall be designed maintain guidance with the loss
of the roller.
- Car Balance:
Provide mounting locations and additional weight for balance of the
elevator.
- Counterweight
Guide Rails: Provide standard T-type steel rails with
brackets for attachment to building structure. Provide any backing or
intermediate tie brackets.
- Counterweight
Guide Assemblies: Provide roller-type which allows
front-to-back and side-to-side adjustment. Each arm shall be spring
mounted with adjustable stops. Rollers shall operate at less than 500
rpm. Guide assemblies shall be designed maintain guidance with the loss
of rollers.
- Counterweight
Frame: Provide steel frame with rods for counterweights.
Provide sufficient means to hold counterweights and provide quiet
operation.
- Counterweights:
Provide sufficient number and type of weights as
required for the motion control system. Weights shall be designed for
the counterweight frame and have holes for the rods. Rods shall be
secured by cotter pins through the locknuts.
- Counterweight
Guards: Provide steel guard for counterweight area in pit.
- Safety and Buffer Systems:
- General:
Provide material from ThyssenKrupp Elevator, Hollister-Whitney Elevator
Corp., KONE Inc. or Otis.
- Governors:
Provide centrifugal-type with bi-direction switches. Provide new test
data tags.
- Safeties:
Provide flexible guide clamp type. Provide new test data tags.
- Governor Tension
Sheaves: Provide standard sheave with bracket mounted
to the guide rails. Provide pivots for free movement and proper tension.
- Car Buffers:
Provide oil type mounted in the pit with protective
covers. Provide switch to prevent operation of the elevator should the
buffer not be fully extended. Provide new test data tags.
- Counterweight
Buffers: Provide oil type mounted in the pit with
protective covers. Provide switch to prevent operation of the elevator
should the buffer not be fully extended. Provide new test data tags.
- Rope Systems:
- General: Provide material from Bethlehem Wire
Rope/Williamsport Wirerope Works, Inc. or Macwhyte Company
- Hoist: Provide a minimum of four ropes with a minimum
diameter of ½". Provide data tag.
- Governor: Provide one rope with a minimum diameter 3/8".
Provide data tags.
- Shackles: Provide wedge-type babbittless type at both ends.
- Hoist-way Entrance Assemblies:
- General: Provide
material from Dover Elevator Company, Hauenstein & Burmeister, Montgomery Elevator Company or Schindler Elevator Company.
- Entrance Frames:
Provide #4 brushed stainless steel bolted type.
Provide UL label on hoist-way side of entrance frame and transom.
- Door Panels:
Provide #4 stainless steel sandwich type without binder
angles. Provide matching or integral sight guards. Provide door panels
with rubber astragal to cushion impact. Provide UL label on hoist-way
side of door panel. Provide 4" high floor marking on hoist-way side of
one door panel.
- Sills: Provide
extruded aluminum with grooved surface. Provide support angles which
require minimal grouting.
- Entrance
Markings: Provide plates on both sides of the hoist-way
entrance centered 60" above the finished floor bolted from the back of
the plate through the entrance frame. All floors shall be identified by
2" high raised numbers/letters/symbols and Braille.
- Escutcheons:
Provide hole in hoist-way door panel to allow special tool
for releasing interlock for each elevator at each floor.
- Fascia: Provide
standard fascia.
- Cab Assemblies:
- General: Provide
material from Dover Elevator Company, Eklund,
Hauenstein & Burmeister, G&R, Globe Architectural, Montgomery
Elevator Company or Schindler Elevator Company.
- Shell: Provide
reinforced 14-gage steel with black baked enamel finish. Apply sound
deadening to exterior.
- Canopy: Provide
reinforced 12-gage steel with white baked enamel finish.
- Suspended
Ceiling: Provide six (6) translucent panels in an aluminum frame and
size to match reveals between wall panels.
- Side and Rear
Walls: Provide plastic laminated removable panels.
Provide three panels on side walls and two panels on rear wall.
- Transom:
Provide #4 brushed 14-gage stainless steel.
- Front
Return/Entrance Columns: Provide #4 brushed 14-gage stainless
steel. Entrance columns shall be separate. Entire front return shall
swing on concealed hinges. Provide engraving for No Smoking, Capacity,
Elevator Number and Emergency Communication. Engrave Firefighter's
Service Operation instructions as required.
- Door Panels:
Provide #4 brushed stainless steel sandwich-type without binder angles.
- Sill: Provide
extruded silver nickel with grooved surface. Provide support angles
which require minimal grouting.
- Handrails:
Provide one line of #4 brushed 2" by 3/8" stainless steel
bars on all three sides with returned ends. Mounting shall be through
the car walls from the back and top of handrails shall be 32" above
finished door.
- Emergency
Lighting: Provide battery unit with solid-state charger to
operate its alarm bell and a minimum of two cab lights. Lights shall be
part of normal lighting system and shall properly illuminate main car
station.
- Emergency Exit:
Provide hinged hatch for evacuation of the elevator
through the top of the elevator. Provide contact to prevent operation
of the elevator when the hatch is not closed.
- Ventilation:
Provide Morrison "PE" multi-speed exhaust blower for proper air flow
through elevator cab.
- Signal Systems:
- General:
Provide material from Adams Elevator Equipment Company, ThyssenKrupp
Elevator, KONE Inc. or Otis.
- Main Car Station
- Car Position
Indicator: Provide 1" high digital segmented type with
direction indicators representing the floor served and the direction of
travel. Provide MH-110 model.
- b.
Pushbuttons: Provide 1-1/8" flush pushbuttons with white LED
illumination. Provide standard pushbuttons for each floor served which
illuminate to indicate call has been registered. Provide emergency
control pushbuttons for alarm, door open, door close, telephone and
floor passing signal.
- Pushbutton
Markings: All pushbuttons shall be identified by raised
numbers/letters/symbols and Braille. Floor pushbuttons and floor
passing signal pushbutton shall have a 5/8" high designation in the
face of each button. All other pushbuttons shall have 1/8" high
designations in the face of each button for identification.
- Firefighter's
Service Controls: Provide keyed switch, light jewel, audible
solid-state signal and call cancel pushbutton.
- Emergency
Communication: Mount vandal-resistant telephone unit provided by Owner
in car station. Phone shall be programmed to signal Security
Department. Phone shall be capable of operating with the remote
monitoring system.
- Floor
Passing Signal: Provide adjustable audible electronic tone which sounds
each time the elevator passes a floor. Pushbutton shall be identified
by the letter "S" and shall activate passing tone for entire trip until
elevator reverses direction.
- Location:
Pushbuttons shall be located between 35" and 48" above the finished cab
floor. Emergency control pushbuttons shall be grouped at the bottom.
Firefighter's Service controls shall be grouped above the pushbuttons.
Emergency communication device shall be behind a round grille with
1/16" holes above the firefighter's service controls.
- Service Cabinet:
- Access: Provide
a flush, keyed #4 brushed stainless steel door with
window for Certificate of Inspection. Window size shall be identical to
local certificate size.
- Controls:
Provide switches for Stop, Inspection, Independent Service, Lighting
and Fan. Provide test button for Emergency Lighting.
- Location:
Cabinet shall be located below the main car station.
- Hall Lanterns:
Provide 2-1/2" high triangular type with #4 brushed
stainless steel faceplates located adjacent to each hoist-way entrance.
Provide adjustable audible electronic tone.
- Hall Stations:
Provide one #4 brushed stainless steel stations per
floor with 1-1/8" standard pushbuttons with white LED illumination.
Hall Stations shall be typically flush mounted.
- Firefighter's
Signs: Provide one #4 brushed stainless steel sign above
each hall station with wording and symbol as contained in Appendix H.
- Hoist-way Access
Stations: Provide switch with #4 brushed stainless
steel faceplates at each terminal located adjacent to the hoist-way
entrance.
- Firefighter's
Service Station: Provide at the main firefighter's floor
installed per local requirements. Engrave firefighter's service
instructions as required in #4 brushed stainless steel faceplate.
- Fire Control
Panel: Provide #4 brushed stainless steel faceplate recess
mounted above the main floor hall station with the following:
- ½" high
LED segmented position indicators with direction arrows for each
elevator.
- Standby power
manual override key switches with collars for each elevator.
- Power light for
each elevator.
- Firefighter's
telephone jack.
- Firefighter's
Key Box: Provide surface mounted type with #4 brushed
stainless steel door. Provide keys and mount per local requirements.
- Pit Emergency
Stop Switch: Provide with red switch.
- Wiring:
- General:
Provide material from Siecor/Republic Wire and Cable.
- Conductors:
Provide new copper wiring throughout, including motor leads. There
shall be no slices.
- Traveling
Cables: Provide a minimum of two cables per elevator. The
cables shall have a flame retardant and moisture resistant outer cover.
Provide pads where necessary to prevent damage to the cables during
operation of the elevator.
- Terminals:
Provide permanent identification at all connections.
- Spares: Provide
an additional 10% conductors for future use. Provide
four additional twisted shielded pair conductors between the machine
room and the main car station. Tag conductors as "SPARES".
- Initial Site Review
- General:
Contractor shall thoroughly review all elevator areas before commencing
work.
- Dimensions:
Contractor shall verify proper space has been provided for
elevator equipment in the machine room, hoist-way and pit areas.
Contractor shall also verify that these areas are ready for the
installation of the elevator equipment.
- Clearances:
Contractor shall verify proper clearances for the elevator equipment
can be maintained within the space provided.
- Electrical:
Contractor shall verify proper electrical power has been
provided. Temporary power of the same characteristics as the permanent
power shall be used if available.
- Environmental:
Contractor shall verify proper operating environment has been provided.
- Variations:
Contractor shall provide written notification of any and
all conditions which will prevent producing satisfactory work within
the schedule.
- Acceptance:
Contractor shall accept conditions prior to commencement of
work. Start of work shall be interpreted as acceptance of conditions.
- Transportation and Storage:
- General:
Contractor shall properly protect equipment and architectural finishes
during transportation and storage.
- Transportation:
Contractor shall deliver and store materials in original protective
packaging.
- Storage:
Contractor shall store equipment in the machine room Any
storage outside the machine room shall be coordinated with the Owner.
- Installation:
- General:
Contractor shall perform all work in a first class work workmanship
manner.
- Standards:
Contractor shall install equipment per Manufacturer's standards and in
accordance with referenced codes.
- Tolerances:
Contractor shall install equipment per Manufacturer's standards and in
accordance with referenced codes.
- Maintainability:
Contractor shall install equipment so components may
be easily accessed for removal during maintenance and repair.
- Field Welding:
Contractor shall utilize certified welders. Oxidation
and residue shall be chipped and cleaned away. All welds shall be wire
brushed and painted with two coats of primer prior to finished coat.
- Unused
Equipment: Contractor shall remove all unused equipment.
- Lubrication:
Contractor shall lubricate all equipment.
- Wiring:
Contractor shall wire equipment as indicated on the electrical
wiring diagrams. Corresponding signals shall both illuminate when
either button is registered.
- Coordination:
Contractor shall coordinate all Work-Not-Included scheduled during the
installation period.
- Protection:
Contractor shall advise Owner of protection procedures to
prevent damage or deterioration of work completed during the remainder
of the installation period.
- Adjustments:
- General:
Contractor shall properly adjust the components provided.
- Design
Parameters: Contractor shall adjust the elevator to meet the design
parameters.
- Guide Rails:
Contractor shall realign car and counterweight guide rails
vertically with tolerance of 1/16". All connections shall be checked
and tightened. Joints shall be secured without gaps. Any irregularities
on the machined surface shall be filled, sanded and filed to a smooth
surface.
- Balance:
Contractor shall balance elevators front-to-back and
side-to-side to equalize pressure of roller car guide rollers on the
car guide rails.
- Guide
Assemblies: Contractor shall adjust car and counterweight guides
to maintain roller contact with the guide rails regardless of load or
position in hoist-way
- Testing:
- General:
Contractor shall test the elevator in accordance with applicable codes.
- Brakes:
Contractor shall test the brakes with maximum load.
- Governors:
Contractor shall test the governors.
- Safeties:
Contractor shall test the safeties with full load at full speed.
- Buffers:
Contractor shall test the buffers with full load at maximum speed.
- Cleanup:
- General:
Contractor shall keep work areas orderly and free from debris during
the installation.
- Daily Removal:
Contractor shall remove packaging and other materials on a daily basis
as equipment is installed.
- Daily Cleaning:
Contractor shall clean work areas on a daily basis of dirt, oil and
grease.
- Final Cleaning:
Contractor shall clean machine rooms, controllers,
hoist-ways, pits, hoist-way equipment, hoist-way entrance assemblies,
pit equipment, door operating equipment, cab enclosures and fixtures of
dirt, oil, grease and finger marks prior to acceptance review.
- Painting and Finishes:
- General:
Contractor shall provide painting and finishing of materials provided.
- Equipment:
Contractor shall clean and paint all equipment which is
provided with one coat of installer's standard enamel unless the
equipment has a baked enamel or special architectural finish. Stencil
paint 4" high elevator number on the mainline disconnect, car lighting
disconnect, each control cabinet, crosshead and car buffer.
- Guide Rails:
Contractor shall clean and paint the shank and base of the
T-Section of the guide rails with one field coat of black Rustoleum
- Equipment
Areas: Contractor shall paint the machine room and pit floors.
- Field
Refinishing: Contractor shall finish any metal work provided.
- Field Retouch:
Contractor shall paint surfaces damaged during
installation with the original color and blend-out any variations.
- Field Quality Control:
- General:
Contractor shall have the work at the location checked during the
course of the installation.
- Progress
Reviews: Contractor shall provide personnel for review. Corrective work
required shall be accomplished as directed.
- Inspections:
Contractor shall complete all corrective work identified by Code
Authority during acceptance inspection prior to Acceptance Review.
- Acceptance
Reviews: Contractor shall provide personnel for reviews.
Contractor shall complete all corrective work identified prior to Final
Acceptance Reviews.
- Final
Acceptance Reviews: Contractor shall provide personnel for reviews to
verify completion of punchlist.
- Warranty
Review: Contractor shall provide personnel for one warranty review.
- Additional
Reviews: Contractor shall compensate Owner for reviews
should all corrective work identified not be completed as required.
- Warranty Service:
- General:
Contractor shall service the elevators from start of the
Installation Period through one year from Final Acceptance of last
elevator.
- Program:
Contractor shall provide all service, repair and adjustment.
Contractor shall also provide service logs, callback logs and repair
logs for the warranty period.
- Callbacks:
Contractor shall provide emergency callback service 24-hour,
7-day-a-week at no additional cost. Contractor shall have a mechanic at
the location within two (2) hours during regular hours and within two
(2) hours for all other callbacks after notification to the Contractor.
- Vandalism:
Owner shall be responsible for service costs due to vandalism.
14 24 00 HYDRAULIC ELEVATORS
- Summary:
- Specify the
scope of work in terms of numbers and groups of elevators
and define the applicable components from the following list:
- Hoist way
entrances, operational and control systems, ADA provisions,
power unit assembly, jack unit assemblies, door operation systems, door
protection systems, car assemblies, cab assemblies, signal system,
furnishing of service/diagnostic laptop computer, providing adjuster
level training and providing one year service warranty.
- Machine Room Work Provided by Others:
- Enclosure:
Fire-rated walls according to the code shall be provided to isolate
elevator equipment from other equipment.
- Access:
Fire-rated door shall be provided which is self-closing and
self-locking.
- Lighting:
Adequate lighting shall be provided in the machine room. One
light switch will be provided on the lock-jamb side of the machine room
entrance door.
- Cooling: Air
conditioning shall be provided to prevent room from
exceeding the maximum equipment operating temperature requirements.
- Heating: Heater
shall be provided to prevent room from falling below the minimum
equipment operating temperature requirements.
- Duplex Outlet:
One duplex outlet with dedicated circuit shall be provided in the room.
- Hoist-way Work by Others:
- Enclosure:
Fire-rated wall shall be provided. Front wall shall be constructed
after entrance frames have been installed.
- Alignment:
Hoist-ways shall be provided which is plumb within 1/2 inch.
- Painting:
Exposed side of hoist-way walls shall be taped and painted.
- Projections:
Beveled guards shall be provided where the side or rear wall projects,
recedes or is set back more than 2 inches.
- Pit Access:
Ladders shall be provided in pits.
- Venting:
Venting shall be provided to prevent accumulation of smoke and gases as
required.
- Sump Pump:
Refer to Standards Section 22 14 29 (Sump Pumps).
- Electrical Requirements by Others:
- Mainline
Disconnects: One lockable, fused three-phase mainline
disconnect of specified voltage shall be provided for each elevator in
the machine room.
- Cab Lighting
Disconnect: One fused single-phase service with switch shall be
provided for the elevator in the machine room.
- Cab Flooring:
- Flooring: Shall
be provided in elevator cabs by general contractor.
- Cab Communications Requirements:
- Telephone
Service: Specify the electrical contractor to provide ¾ inch
conduit, from the nearest telephone closet (FDF), 4 pair CAT 5
telephone cable and a "D-MARK" junction box near the controller of each
elevator for the purpose of providing ADA compliant telephone service
in each cab. Final trimming, testing and programming shall be performed
by University Telecommunication Department.
- Emergency
Telephone Device: Standard University Emergency Telephone
Unit (ETU), hands free, ADA compliant, will be provided by the
University. Elevator contractor shall make necessary cut out, and
provide mounting flanges with 4 tapped holes, so that the unit could be
secured flush to either the front return/entrance swing column unless
shown otherwise on drawings. The University will loan a prototype of
the ETU to the elevator manufacturer contractor for making proper cut
outs and mounting reinforcement mechanism.
- Quality Assurance:
- Qualified
Bidders: Contractor shall be required to submit the following certified
information with pre-qualification documents:
- Contractor is
currently engaged in the manufacturing of elevator
equipment, installation and repairs of elevators and has been for the
previous twenty-five (25) years.
- Contractor shall
have technical qualifications of at least ten (10)
years installing microprocessor-based elevator equipment. Qualification
shall be based on having trained supervisory and installation personnel
and the facilities to install the elevator equipment proposed in the
Chicago area.
- Contractor
shall submit a list of installations totaling 100 completed elevators
where the elevator equipment was similar to specified for this
installation.
- Contractor
shall submit a list of five or more local (in the Chicago area)
installations where all the elevator equipment similar to specified
herein has been completed.
- Contractor will
provide all major components manufactured by his company for unified
responsibility.
- Contractor is
prepared to furnish to the University the service laptop
PC needed to troubleshoot, service and test the controller, door
operator and signals and that he is prepared to update the servicing
laptop at no cost to the university. Also, that he is prepared to
provide adjuster level training to University's elevator mechanics in
the use of the service laptop.
- Code Compliance:
- General:
contractor shall comply with most-stringent applicable
provisions of the following Codes, Standards and Laws including
revisions and changes in effect on dated of these specifications.
- Elevator:
- ASME A17.1 -
Safety Code for Elevators and Escalators.
- ASME A17.2 -
Inspector's Manual.
- ASME A17.3 -
Safety Code for Existing Elevators and Elevators.
- Electrical:
- NFPA 70 -
National Electrical Code.
- Building:
- City of Chicago
Building Code
- Life Safety:
- NFPA 101 - Life
Safety Code
- City of Chicago
Fire Prevention.
- Handicapped
accessibility:
- Americans with
Disability Act.
- Illinois
Environmental Barriers Act.
- ANSI A-117.1 -
Specifications for making Building and Facilities Accessible to, and
Usable by, the Physically Handicapped.
- Laws: Any other
Ordinances and Laws applicable within the governing jurisdiction.
- Pre-Installation Submittal:
- General:
Require the contractor to assemble complete submittal package within 15
days of Award of Contract.
- Product Data:
Require the Contractor to submit six (6) copies of the
manufacturer's specifications and installation instructions for each
product furnished, especially the elevator car enclosure, machine room
layout and hoist-way entrances.
- Power Data:
Require the Contractor to provide electrical calculations for all
three-phase and single-phase feeder requirements.
- Test Data:
Require the Contractor to provide certified laboratory test
reports on components as specified or required by referenced codes.
- Key Switches and
Keying: Require that the elevator shall furnish "BEST" key switches and that the contractor shall furnish cylinders with
construction cores. Also, specify the contractor shall furnish to the
University the construction core control key. University will key the
locks according to UIC Facilities Management procedure.
- Material
Samples: Require the contractor to furnish three (3) samples of each
material furnished.
- Initial Shop
Drawings: Require contractor to submit one (1) mylar and
six (6) copies of the equipment arrangement in the machine room, pit
and hoist-way, provide plans, elevations, sections and details of
assemblies, erection, anchorage, and equipment location for review and
approval by A/E.
- Submittal
Response: Specify the one Mylar and two copies shall be
returned to the Contractor within 10 days. Submittal response is not
justification for revision of delivery or installation schedules
without prior written notification
- Revised Shop
Drawings: Specify that contractor shall incorporate changes and return
one copy within 7 days.
- Permits, Inspections and Reviews:
- General: Specify
that contractor shall coordinate all inspections and
reviews with University and City of Chicago Bureau of Elevator
Inspection.
- Permits: Specify
that contractor shall obtain and pay for permits,
licenses and inspection fees necessary to complete the elevator
installation.
- Inspections:
Contractor shall make all tests required by the referenced
codes and/or inspection authorities. Contractor shall notify inspection
authorities with sufficient notice and have inspection performed prior
to reviews. Inspection delays are not justification for revision of
installation schedules without prior written notice.
- Reviews:
Contractor shall provide the personnel for acceptance reviews
and final reviews indicated in the Contract Documents. Contractor shall provide 7 days
notice to the Owner for each review.
- Post-Installation Submittal:
- General:
Contractor shall assemble complete submittal package within 30 days of
final acceptance of the final elevator.
- Final Shop
Drawings: Contractor shall provide four (4) complete sets of "AS INSTALLED" drawings. All changes shall be revised on the
manufacturer's drawings. No hand written changes will be accepted.
- Electrical
Wiring Diagrams: Contractor shall provide six (6) complete
sets of "AS INSTALLED" electrical wiring diagrams (EWDs). All changes
shall be revised on the manufacturer's drawings. No hand written
changes will be accepted.
- Maintenance
Manuals: Contractors shall provide four (4) copies of
neatly bound manuals including instructions explaining all operating
features, parts lists, recommended spare parts, lubrication charts and
recommended maintenance schedule. Contractor shall also provide three
(3) separate copies of the adjustment, system overview, service tool
and troubleshooting manuals.
- Keys: Contractor
shall provide the construction core key and three (3)
sets of properly tagged keys to operate all keyed switches and locks
upon completion of the first elevator.
- Service Tool:
Elevator Contractor shall furnish to the University two
(2) laptop PC service tool with necessary software needed for
adjusting, trouble shooting and performing safety and operational
tests. It must be emphasized that the service tool shall be used
exclusively by University elevator mechanics and it shall be used only
for the elevator(s) provided under the scope of this project. The
service tool shall be delivered to the University elevator foreman on
or before the training session described by these standards. All
necessary updating of this tool will be performed at no cost to
University.
- Warranty:
- Period:
Contractor shall guarantee that the materials and workmanship
of the elevator equipment installed under these specifications shall be
first-class in every respect. Contractor shall make good all defects,
not due to ordinary wear and tear or improper use, which may develop
within one year after the final acceptance.
- Periodic
Examination: During the Warranty period the contractor shall
lubricate all parts, examine all components of the elevators for
conformance with specified design features such as, the door timings,
checking bulbs of signals, group operation, speed of elevator, etc. The
periodic examination will be conducted at least for one (1) hour every
month for each elevator. Prior to performing the examination the
contractor shall notify the UIC elevator foreman at least 2 days
advance of the scheduled examination date. Failure to provide this
examination will result in proportionate extension of warranty period.
- Service:
Contractor shall provide call back warranty service at no cost
to the University, with a response time not to exceed 2 hours, as
follows:
- Maintenance
work, including 24 hour-per-day, 7 day-per week emergency
call back repair service, shall be performed by trained employees of
the elevator contractor.
- Contractor will
maintain an accurate log of all service calls, including details of the
malfunctions and repairs performed.
- At the end of
the warranty period the service call log will be turned over to the
University Elevator Foreman.
- End of Warranty
period Review: Contractor shall provide personnel for
one warranty review. Owner may schedule this review anytime during the
warranty period. Contractor shall provide any modifications to the
elevator equipment and any adjustment necessary to meet requirements of
the Contract Documents identified during the warranty review within 30
days of notification.
- Training:
- General:
Elevator Contractor shall provide training to representatives of the
Owner as follows:
- On-Site:
Contractor shall provide two (2) adjuster level training
sessions of 40 hours each to UIC elevator mechanics on University
premises. UIC Facilities Management will make necessary
on-campus/on-site arrangement for this training. Training shall include
detailed overview of operational control system, motion control system,
door control system, signal system, trouble shooting, servicing and
periodic maintenance required. This training shall also include the
training in the use of the Laptop Service Tool for adjusting, testing,
down loading operational history, programming floors, etc.
- Specify the following for each elevator:
- Quantity.
- Type.
- Capacity.
- Speed.
- Stops.
- Openings and
Landings.
- Floors Served.
- Travel.
- Entrance Size.
- Entrance Type.
- Platform Size.
- Cab Height.
- Door Type.
- Operation
System.
- Power
Characteristics.
- Special Features.
- Approved
Manufacturers: Specify that elevators shall be (pre-engineered,
customized or combination of the two) products from the following
manufacturers:
- Otis.
- ThyssenKrupp.
- KONE Inc.
- Design Parameters: The elevator system shall be designed,
installed and adjusted to meet the following requirements:
- Flight Time: The
elevators shall arrive at the next typical floor with
the doors open two-thirds within (calculated flight time) seconds from
the start of door closing movement. This shall be accomplished
regardless of load or direction of the elevator.
- Door Motion
Times: The elevators shall open its doors within
(calculated door open motion time) seconds. The elevators shall close
its doors within (calculated door close motion times) seconds or the
minimum allowed by Code, whichever is greater. Door times are measured
from the start of movement until movement is stopped.
- Floor Accuracy:
The elevators shall stop within 3/8" of floor
regardless of load or direction and re-level to within 3/8" during
loading/unloading.
- Speed: The
elevators shall operate within 10% of the contract speed regardless of
load or direction.
- Ride: The
elevators shall operate smoothly, with less than 15 mg
horizontal acceleration, less than 2.0 feet per second-squared vertical
acceleration and less than 4.0 feet per second-cubed vertical jerk.
- Noise: The
elevators shall operate quietly, with less than 55 dBa
within the cab with the doors closed, 60 dBa with door operation and 65
dBa within the machine room. Noise is measured with a Dranatz Sound
Meter on the C scale with the background noise less than 45 dBa.
- Electrical:
- Mainline
Feeders: The elevator shall have a starting current of less
than (calculated stalling current) amps and a running current of less
than (calculated running current) amps with the three-phase incoming
voltage being maintained within 6 10% of 480 Volts AC and within 3% of
60 cycles.
- Mainline
Harmonics: The elevator shall add not more than 5% harmonic distortion
and shall meet the requirements of IEEE 519.
- Lighting
Feeders: The elevator shall have a lighting and fan current of
less than 20 amps with the single-phase voltage being maintained within
l0% of 120 Volts AC.
- Environment:
- Temperature:
The elevators shall be capable of operating properly with the
temperature between 55 and 95 degrees Fahrenheit.
- Humidity: The
elevator shall be capable of operating properly with the
humidity being maintained below 90% non-condensing in equipment room.
- Heat Emissions:
- Machine Room:
The elevator shall not produce more than (calculated equipment heat
emissions) BTU's total in this area.
- Hoist-way: The
elevator shall not produce more than (calculated equipment heat
emissions) BTU's total in this area.
- Control Systems:
- Operational
Control:
- Group Operation:
Provide group operational control to operate all the
elevators in each group automatically in response to car and hall
calls. The elevators shall be assigned calls as they are registered.
The closest elevator shall be assigned a hall call based on the
estimated time of arrival (ETA). Penalties shall be given to long
established hall calls and bonuses for coincident calls. The elevator
shall stop for hall calls only in the direction of travel. The elevator
shall reverse automatically in response to a hall call in the opposite
direction of travel. The elevator shall reverse without door cycle
after hold open time has expired when there is no further demand in the
direction of travel and shall close after the additional hold open time
has expired. The elevators shall zone after the last call is answered.
There shall be one zone for each elevator in the group. The lobby zone
shall be the first zone filled.
- Firefighter's
Service Operation: Provide means to operate the elevators
during an emergency. Also provide connections for future smoke detector
activation of lobby and alternate floor automatic return.
- Inspection
Operation: Provide means to operate the elevator at reduced
speed from the top of the elevator. Activation of Inspection Operation
shall remove the elevator from service.
- Independent
Service Operation: Provide means to operate the elevator in
response to only car calls. Close doors by holding a car call until
doors are completely closed. Activation of Independent Service
Operation shall remove the elevator from service. The elevator shall
park with the doors open at the last floor served.
- Hoist-way Access
Operation: Provide means to operate elevator at the
top and bottom terminals at reduced speed with both the hoist-way doors
and the car doors open. Terminal access shall be zoned.
- Car-To-Terminal
Operation: Provide means to initiate a demand at e
terminal when the access key switch is activated. The elevator shall
arrive at the terminal without activating the hall lantern or canceling
the hall call. The elevator shall remain at the terminal for 15 to 30
seconds to allow the elevator to be placed on inspection operation. In
the event that the elevator not be removed from service during the
allotted time, the elevator shall return to group operation.
- Oil Temperature
Control Operation: Provide means to maintain proper
operating temperature of hydraulic oil for consistent operation of the
elevator. When oil temperature is detected below the proper range and
there are no hall calls or car calls, the elevator shall be
automatically lowered to the lowest landing and with the doors closed,
oil may be bypassed with the pump motor running until the oil is within
the proper range. The elevator shall immediately respond to any hall
calls or car calls and shall return this feature when all calls have
been answered.
- Delayed
Operation: Provide means to remove an elevator from group
operation in the event that it is delayed and cannot respond to demands.
- Programmed
Shutdown Operation: Provide means to stop the elevator at
the next floor, open the doors and remove the elevator from service.
The controller shall prevent the operation of the elevator until the
problem is manually reset. This operation shall activate by the oil
over-temperature monitor, machine room over-temperature monitor and
reduced incoming power monitor.
- Hall Button
Failure Operation: Provide means to maintain the
registration of hall calls in the event all the elevators are removed
from service for less than 5 minutes except firefighter's service
feature. After 5 minutes all hall calls shall be canceled and remain
canceled. The timer shall be reset every time one elevator is back in
service.
- Power Loss
Operation: Provide means to automatically return one
elevator to the lowest landing in the event of a power loss. After the
elevator has returned to the lowest landing, the elevator shall open
and the elevator shall be removed from service until power is restored.
The open door button shall remain operational after doors are closed.
- Back-up
Operation: Provide means to maintain elevator service in the
event that the control system cannot assign hall call demands.
- Motion Control:
- Automatic
Operation: Provide motion control which automatically
decelerates. Levels and stops the elevator in response to a call.
- Reduce Current
Starting Operation: Provide means to start the power
unit with reduced current by utilizing a wye-delta configuration for
starting the pump motor or utilizing solid-state starting of the pump
motor.
- Re-Leveling
Operation: Provide means to level the elevator after the elevator has stopped to
maintain floor accuracy.
- Low Oil
Operation: Provide means to monitor for low oil in the tank. When low
oil is detected. The elevator shall be automatically lowered to the
bottom terminal. Open the doors and remove the elevator from service
until manually reset.
- Over-travel
Limiting Operation: Provide means to prevent the operation of the elevator
when it travels beyond the leveling zone at a terminal floors. The
limits switches shall operate quietly.
- Door Control:
- Automatic
Operation: Provide door control which automatically opens and closes.
-
Force Limiting Operation: Provide means to open the door pressure while
closing to a maximum of 30 pounds (measured from rest) and a maximum of
7.5 foot-pounds kinetic energy.
-
Reduced stall Force Operation: Provide means to reduce the force
exerted on the doors during a stall condition. Door pressure shall be
zero pounds after one second.
- Reduced Speed Closing Operation: Provide means to reduce the speed
during closing to a maximum of 2.5 foot-pounds kinetic energy. Doors
shall close at reduced speed during Firefighter's Service as required
by the code.
- Door Hold
Operation: Provide separately adjustable timers to vary the time the
doors hold open as follows:
- Car Call Timer:
The amount of time the doors shall be held in response to a hall call
shall be between 3.0 and 6.0 seconds.
- Hall Call Timer:
the amount of time the door shall be held open in
response to a hall call or coincidental car call shall be between 4.0
and 8.0 seconds.
- Interrupted
Screen Timer: The amount of time the door shall be held
open after the screen is reestablished shall be between 1.0 and 3.0
seconds. The timer shall be reset with each interruption of the door
screen.
- Door Reversal
Timer: The amount of time the door shall be held open
after doors are fully reopened. Timer setting shall be between 0 and
3.0 seconds.
- Nudging Timer:
The amount of time the doors shall be held open before
sounding an audible tone. Timer setting shall be between 20 and 30
seconds.
- Initial Timer
Settings: Timers shall be initially set to the minimum
allowed by handicapped accessibility standards within the range. Car
call and door close buttons shall have no effect on timers.
- Door Stall
Operation: Provide means to reopen doors in the event that
the doors do not close all the way within 30 seconds of closing
operation. Provide means to remove the elevator from service after the
third unsuccessful attempt.
- Controller
Assemblies:
- General:
Provide material from ThyssenKrupp, KONE Inc., or Otis.
- Microprocessor:
Provide a microprocessor-base unit for operational and
communication functions. Provide ThyssenKrupp TAC 20 model. KONE Inc.
Miprom I, Otis Elvonic 211.
- Software:
Provide nonproprietary type.
- Service Tool:
Provide all service tools require for troubleshooting, adjusting and
testing.
- Position
Sensing: Provide digital solid-state type. Provide a system
that does not utilize a stationary tape in the hoist-way A LED-type
position indicator shall be located in the machine room.
- Contactors and
Relays: Provide solid-state type which shall be sized to
insure proper conductivity and reliable operation. Contactor shall be
as manufactured by Nordic or equal.
- Identifications:
Provide permanent markings for all components,
including size and type of fuses, identical to those symbols found on
the Electrical Wiring Diagrams.
- Isolation
Transformers/Filters: Provide transformers and filters to isolate noise
from the electrical system.
- Labeling:
Provide UL, CSA or ASME A.17.5 label.
- Power Unit Assemblies:
- Valves:
Provide a four valve unit which shall be readily accessible for
adjustment. Control valves shall be solenoid operated and shall open
and close gradually for smooth motion control. Provide test seal for
relief valve. Provide EECO Model UV 5A or equal.
- Pump: Provide a
non-submersible constant displacement rotary screw type.
- Muffler: Provide
one muffler in the oil line near the power unit to
reduce the pulsations and noise present in the flow of the hydraulic
fluid.
- Vibration Sound
Dampeners: Provide rubber type to isolate the power unit from the
building structure.
- Isolation
Couplings: Provide a minimum of two in the oil line.
- Piping/Oil:
Provide a direct run from the power unit to the cylinder
with a minimum of bends. Provide test data tag. Oil reservoir shall
hold 10 gallons in addition to he oil required to operate the elevator.
- Shutoff Valve:
Provide one manual type in machine room near power unit.
- Jack Assemblies:
- Plunger:
Provide seamless steel type which is accurately ground and polished.
The bottom shall be fitted with a heavy steel disc welded in place with
an extended edge to prevent the plunger from leaving the cylinder.
Provide steel packing gland with bronze guide bearing, wiper ring and
packing.
- Cylinder:
Provide a steel pipe which is machined. The upper end shall have a
machine flange and the lower end shall have a heavy steel bulkhead. A
double wrap of polyethylene tape bonded with a special corrosion
resistant bonding agent shall be provided for protection.
- Casing: Provide
PVC type filled with Niggard 160.
- Jack Hole:
Provide excavation for jack. Hole shall be plumb within I" for every 10
feet or less of depth.
- Channel
Buffers: Provide two spring type mounted to the pit channels on each
side of the cylinder.
- Shutoff Valve:
Provide one manual type in pit near the cylinder.
- Door Operation System:
- General: Provide
material from ThyssenKrupp, Moline Accessories Corporation, KONE Inc.
or equal product from Otis.
- Operator:
Provide high-speed, heavy-duty DC master type operator with digital
velocity and position feedback. Provide a contact on the car door which
shall prevent the operation of the elevator when the car door is not
closed. Provide ThyssenKrupp HD-85 model, MAC DHP model or equal
product from Otis.
- Headers:
Provide steel type shaped to provide stiff flanges.
- Tracks: Provide
removable bar or formed steel with contours to match the hangers. Each
track shall be reversible.
- Hangers: Provide
polyurethane-type with pre-lubricated sealed bearings
which will allow vertical and lateral adjustment of the hoist-way and
car door panels. Each door panel shall have two-point suspension with
separate replaceable hangers. Up-thrust shall be provided to maintain
alignment of the door panels.
- Gibs: Provide
two nylon-type per door panel. Fire stops shall be properly bent down
on hoist-way door panels.
- Interlocks:
Provide an electromechanical device which shall prevent the
operation of the elevator when the hoist-way doors are not closed and
locked.
- Restrictors:
Provide device which restricts the opening of the car doors outside the
unlocking zone.
- Closers:
Provide spirator or sash weight type which shall close the hoist-way
doors from any open position.
- Door Protection Systems:
- General: Provide
material from Janus Elevator Products, Inc.
- Door Screen:
Provide infrared pulsed type which shall initiate door reopening
operation. Provide Panaforty model.
- Controller:
Provide two-relay type which shall allow reduced speed door closing
operation. Provide Panacombi Mark II model.
- Labeling:
Provide UL or CSA label.
- Car Assemblies Guide and Balance Systems:
- General: Provide
material from ThyssenKrupp. KONE Inc., Hollister-Whitney Elevator
Corp., or equal product from Otis.
- Car
Frame: Provide steel plank, cross head and stiles. Provide new Car Top
Inspection Stations with properly covered work light and 3-wire
grounded-type outlet permanently mounted to the cross head of each
elevator. Provide Crosshead Data Tags permanently mounted to the
crosshead. Both the stations and the data tags shall be easily accessed
from tile hoist-way landing.
- Platform :
Provide wood type with paten plate isolation. Fireproof
underside of platform. Recess the floor to receive specified flooring
material.
- Car Guide Rails:
Provide standard T-type steel rails with brackets for
attachment to building structure. Provide any backing or intermediate
tie brackets.
- Car Guide
Assemblies: Provide roller-type which allows front-to-back
and side- to-side adjustment of each guide. Each arm shall be spring
mounted with adjustable stops. Rollers shall operate at less than 250
rpm. Guide assemblies shall be designed to maintain guidance with the
loss of the rollers.
- Car Balance:
Provide mounting locations and additional weight for balance of the
elevator.
- Buffer Systems:
- General: Provide
material from ThyssenKrupp, Hollister-Whitney Elevator Corp., KONE
Inc., or equal product from Otis.
- Car
Buffers: Provide oil type mounted in the pit with protective covers.
Provide switch to prevent operation of the elevator should the buffer
not be fully extended. Provide new test data tags.
- Hoist-way Entrance Assemblies:
- General: Provide
material from ThyssenKrupp, Hauenstein & Burmeister, KONE Inc.,
Otis.
- Entrance
Frames: Provide #4 brushed stainless steel bolted type. Provide UL
label on hoist-way side of entrance frame and transom.
- Door Panels:
Provide #4 stainless steel sandwich type without binder
angles. Provide matching or integral sight guards. Provide door panels
with rubber astragals to cushion impact. Provide UL label on hoist-way
side of door panel. Provide 4 " high floor marking on hoist-way side of
one door panel.
- Sills: Provide
extruded silver nickel with grooved surface. Provide support angles
which require minimal grouting.
- Entrance
Markings: Provide plates on both sides of the hoist-way
entrance centered 6()" above the finished floor bolted from the back of
the plate through the entrance frame. All floors shall be identified by
2" high raised numbers/letters/symbols and Braille.
- Escutcheons:
Provide hole in hoist-way door panel to allow special tool
for releasing interlock for each elevator at each floor.
- Fascia: Provide
standard fascia.
- Cab Assemblies:
- General:
Provide material from ThyssenKrupp, Eklund, Hauenstein &
Burmeister, G&R, Globe Architectural, KONE Inc. or Otis.
- Shell: Provide
reinforced 14-gage steel with black baked enamel finish. Apply sound
deadening to exterior.
- Canopy: Provide
reinforced 12-gage steel with white baked enamel finish.
- Suspended
Ceiling: Provide six (6) translucent panels in an aluminum frame and
size to match reveals between wall panels.
- Side and Rear
Walls: Provide three panels on side walls and two panels
on rear wall. A/E shall specify the materials and design of the panels.
- Transom:
Provide #4 brushed 14-gage stainless steel.
- Front
Return/Entrance Columns: Provide #4 brushed 14-gage stainless
steel. Entrance columns shall be separate. Entire front return shall
swing on concealed hinges. Provide engraving for "No Smoking", Capacity
in pounds, 5 digit elevator number as specified by UIC.
- Door Panels:
Provide #4 brushed stainless steel sandwich-type without binder angles.
- Sill: Provide
extruded Silver Nickel with grooved surface. Setting shall allow for
cab flooring material.
- Handrails:
Provide one line of #4 brushed 2" by 3/8" stainless steel
bars on all three sides with returned ends. Mounting shall be through
the car walls from the back and top of handrails shall be 32" above
finished floor.
- Emergency
Lighting: Provide battery unit with solid-state charger to
operate its alarm bell and a minimum of two cab lights. Lights shall be
part of normal lighting system and shall properly illuminate main car.
- Emergency Exit:
Provide hinged latch for evacuation of the elevator
through the top of the elevator. Provide contact to prevent the
elevator from operating when the latch is open.
- Ventilation:
Provide Morrison "OE" multi-speed exhaust blower for proper ventilation
through the cab.
- Signal Systems:
- General:
Provide material from Adams Elevator Equipment Company Vandal
Resistance Series for Dormitories and classroom buildings. Provide
ThyssenKrupp fixtures for all other buildings. Typically specify one
car station for each elevator. Buildings in excess of 12 stories shall
have two (2) car stations.
- Main Car Station:
- Car Position
Indicator: Provide 1" high digital segmented type with
direction indicators representing the floor served and the direction of
travel.
- Pushbuttons:
Provide 1-1/8" flush pushbuttons with white LED
illumination. Typically specify standard pushbuttons for each floor
served which illuminate to indicate call has been registered. For
classroom occupancy buildings specify vandal resistant buttons. Specify
emergency control pushbuttons for alarm, door open, door close,
telephone and floor passing signal.
- Pushbutton
Markings: All pushbuttons shall be identified by raised
numbers/letters/symbols and Braille. Floor pushbuttons and floor
passing signal pushbutton shall have a 5/8" high designation in the
face of each button. All other pushbuttons shall have 1/8" high
designations in the face of each button for identification.
- Firefighter's
Service Controls: Provide keyed switch, light jewel, audible
solid-state signal and call cancel pushbutton.
- Emergency
Communication: Mount vandal-resistant telephone unit provided
by Owner in car station. Phone shall be programmed to signal Security
Department. Phone shall be capable of operating with the remote
monitoring system.
- Floor Passing
Signal: Provide adjustable audible electronic chime tone
which sounds each time the elevator passes a floor. Pushbutton shall be
identified by the letter "S" and shall activate passing tone for entire
trip until elevator reverses direction.
- Location:
Pushbuttons shall be located between 35" and 48" above the
finished cab floor. Emergency control pushbuttons shall be grouped at
the bottom. Firefighter's Service controls shall be grouped above the
pushbuttons. Emergency communication device shall be behind a round
grille with 1/16" holes above the firefighter's service controls.
- Service Cabinet:
- Access: Provide
a flush, keyed #4 brushed stainless steel door with
window for Certificate of Inspection. Window size shall be identical to
local certificate size.
- Controls:
Provide switches for Stop, Inspection, Independent Service,
Lighting and Fan. Provide test button for Emergency Lighting.
- Location:
Cabinet shall be located above the car operating station.
- Hall
Lanterns: Provide 2-1/2" high triangular type with #4 brushed stainless
steel faceplates located adjacent to each hoist-way entrance. Provide
adjustable audible electronic tone.
- Hall
Stations: Provide one #4 brushed stainless steel stations per floor
with 1-1/8" standard pushbuttons or vandal resistant with white LED
illumination.
- Firefighter's
Signs: Provide one #4 brushed stainless steel sign above
each hall station with wording and symbol as required by applicable
code.
- Hoist-way Access
Stations: Provide switch with #4 brushed stainless
steel faceplates at each terminal located adjacent to the hoist-way
entrance.
- Firefighter's
Service Station: Provide at the main firefighter's floor stalled per
local requirements. Engrave firefighter's service instructions as
required in #4 brushed stainless steel faceplate.
- Fire Control
Panel: Provide #4 brushed stainless steel faceplate recess
mounted in the main floor hall station or at a prominent location with
the followings:
- 1/2" high LED
segmented position indicators with direction arrows for each elevator.
- Standby power
manual override key switches with collars for each elevator.
- Power light for
each elevator.
- Firefighter's
Key Box: Provide surface mounted type with #4 brushed stainless steel
door. Provide keys and mount per local requirements.
- Wiring:
- General: Provide
material from Siecor/Republic Wire and Cable.
- Conductors:
Provide new copper wiring throughout, including motor leads. There
shall be no slices.
- Traveling
Cables: Provide a minimum of two (2) 50 pair cables per
elevator. The cables shall have a flame retardant and moisture
resistant outer cover. Provide pads where necessary to prevent damage
to the cables during operation of the elevator.
- Terminals:
Provide permanent identification at all connections.
- Spares: Provide
an additional 10% conductors for future use. Provide
four additional twisted shielded pair conductors between the machine
room and the main car station. Tag these conductors as "SPARES".
- Piping:
- General:
Provide galvanized steel with removable covers.
- Initial Site Review:
- General:
Contractor shall thoroughly review all elevator areas before commencing
work.
- Dimensions:
Contractor shall verify proper space has been provided for elevator
equipment in the machine room, hoist-way and pit areas. Contractor
shall also verify that these areas are ready for the installation of
the elevator equipment.
- Clearances:
Contractor shall verify proper clearances for the elevator equipment
can be maintained within the space provided.
- Electrical:
Contractor shall verify proper electrical power has been
provided. Temporary power of the same characteristics as the permanent
power shall be used if available.
- Environmental:
Contractor shall verify proper operating environment has been provided.
- Variations:
Contractor shall provide written notification of any and
all conditions which will prevent producing satisfactory work within
the schedule.
- Acceptance:
Contractor shall accept conditions prior to commencement of
work. Start of work shall be interpreted as acceptance of conditions.
- Transportation and Storage:
- General:
Contractor shall properly protect equipment and architectural finishes
during transportation and storage.
- Transportation:
Contractor shall deliver and store materials in original protective
packaging.
- Storage:
Contractor shall store equipment in the machine room. Any
storage outside the machine room shall be coordinated with the Owner.
- Installation:
- General:
Contractor shall perform all work in a first class workmanship manner.
- Standards:
Contractor shall install equipment per Manufacturer's standards and in
accordance with referenced codes.
- Tolerances:
Contractor shall install equipment to maintain proper clearances during
the operation of the elevator.
- Maintainability:
Contractor shall install equipment so components may
be easily accessed for removal during maintenance and repair.
- Field Welding:
Contractor shall utilize certified welders. Oxidation
and residue shall be chipped and cleaned away. All welds shall be wire
brushed and painted with two coats of primer prior to finished coat.
- Unused
Equipment: Contractor shall remove all unused equipment.
- Lubrication:
Contractor shall lubricate all equipment.
- Wiring:
Contractor shall wire equipment as indicated on the electrical
wiring diagrams. Corresponding signals shall both illuminate when
either button is registered.
- Coordination:
Contractor shall coordinate all Work-Not-lncluded scheduled during the
installation period.
- Protection:
Contractor shall advise Owner of protection procedures to
prevent damage or deterioration of work completed during the remainder
of the installation period.
- Adjustments
- General:
Contractor shall properly adjust the components provided.
- Design
Parameters: Contractor shall adjust the elevator to meet the design
parameters.
- Guide Rails:
Contractor shall realign car guide rails vertically with
tolerance of 1/16". All connections shall be checked and tightened.
Joints shall be secured without gaps. Any irregularities on the
machined surface shall be filled, sanded and filed to a smooth surface.
- Balance:
Contractor shall balance elevators front-to-back and
side-to-side to equalize pressure of roller car guide rollers on the
car guide rails.
- Guide
Assemblies: Contractor shall adjust car guides to maintain roller
contact with the guide rails regardless of load or position in hoist-way
- Testing:
- General:
Contractor shall test the elevator in accordance with applicable codes.
- Relief Valve
Setting: Contractor shall test the relief valve setting.
- Hoses and
Fittings: Contractor shall test the hoses and fitting for a minimum of
30 seconds.
- Buffers:
Contractor shall test the buffers with full load at maximum speed.
- Painting and Finishes
- General:
Contractor shall provided painting and finishing of materials provided.
- Equipment:
Contractor shall clean and paint all equipment which is provided with
one coat of installer's standard enamel unless the equipment has a
baked enamel or special architectural finish. Stencil paint 4" high
elevator number on the mainline disconnect, car lighting disconnect,
each control cabinet, crosshead and car buffer.
- Guide Rails:
Contractor shall clean and paint the shank and base of the
T-Section of the guide rails with one field coat of black Rustoleum
- Equipment
Areas: Contractor shall paint the machine room and pit floors.
- Field
Refinishing: Contractor shall finish any metal work provided.
- Field Retouch:
Contractor shall paint surfaces damaged during
installation with the original color and blend-out any variations.
- Cleanup:
- General:
Contractor shall keep work areas orderly and free from debris during the
installation.
- Daily Removal:
Contractor shall remove packaging and other materials on a daily basis
as equipment is installed.
- Daily Cleaning:
Contractor shall clean work areas on a daily basis of dirt, oil and grease.
- Final Cleaning:
Contractor shall clean machine rooms, controllers,
hoist-ways, pits, hoist-way equipment, hoist-way entrance assemblies,
pit equipment, door operating equipment, cab enclosures and fixtures of
dirt, oil, grease and finger marks prior to acceptance review.
- Field Quality Control:
- General:
Contractor shall have the work at the location checked during the
course of the installation.
- Progress
Reviews: Contractor shall provide personnel for review. Corrective work
required shall be accomplished as directed.
- Inspections:
Contractor shall complete all corrective work identified
by the Code Authority during acceptance inspection prior to Acceptance
Review.
- Acceptance
Reviews: Contractor shall provide personnel for reviews.
Contractor shall complete all corrective work identified prior to Final
Acceptance Reviews.
- Final
Acceptance Reviews: Contractor shall provide personnel for reviews to
verify completion of punch list.
- Warranty
Review: Contractor shall provide personnel for one warranty review,
- Additional
Reviews: Contractor shall compensate Owner for reviews
should all corrective work identified not be completed as required.
- Warranty Service:
- General:
Contractor shall service the elevators for one year from Final
Acceptance of last elevator of the group.
- Program:
Contractor shall provide all service, repair and adjustment. Contractor
shall also provide service logs, callback logs and repair logs for the
warranty period.
- Callbacks:
Contractor shall provide emergency callback service
24-hours, 7-days-a-week at no additional cost. Contractor shall have a
mechanic at the location within two (2) hours during regular hours and
within two (2) hours for all other callbacks after notification to the
Contractor.
- Vandalism:
Owner shall be responsible for service costs due to vandalism.
14 31 00 ESCALATORS
- Rated Speed: 90 ft./min.
- Initial
Maintenance Service: Beginning at Substantial Completion, provide 12
months' full maintenance by skilled employees of escalator Installer.
Include monthly preventive maintenance, repair or replacement of worn
or defective components, lubrication, cleaning, and adjusting as
required for proper escalator operation at rated speed and capacity.
Provide parts and supplies same as those used in the manufacture and
installation of original equipment.
- Perform
maintenance, including emergency callback service, during normal
working hours.
- Include
24-hour-per-day, 7-day-per-week emergency callback service.
- Response Time:
Two hours or less.
- Subject to compliance with requirements, provide escalators
by one of the following preferred manufacturers.
- Dover Elevator
Systems.
- Fujitec
America, Inc.
- Montgomery
KONE Inc.
- Otis Elevator
Co.
- Schindler
Elevator Corp.
- Thyssen
Elevator Group North America.
- Optional Features:
- Fault Indicator:
Provide escalators with a microprocessor unit that
monitors safety devices, motor temperature, and escalator speed and
records in nonvolatile memory date, time, and device identification if
a safety device is activated or escalator malfunctions. Provide
built-in unit to display recorded information.
- Instruct
Facilities Management maintenance personnel in proper use, operation,
and daily maintenance of escalators. Review emergency provisions,
including procedures to be followed at time of operational failure and
other building emergencies. Train Facilities Management maintenance
personnel in procedures to follow in identifying sources of operational
failures or malfunctions. Consult Facilities Management on requirements
for a complete escalator maintenance program.
14 42 16 VERTICAL WHEELCHAIR LIFTS
- Rise shall be no more than 12 feet.
- Rated load shall not be less than 450 pounds.
- Rated speed shall be no more than 30 feet per minute.
- Enclosures shall be provided to prevent access to underside
of lift when the unit is in the up position.
- Matot and Concord are the preferred manufacturers.
|