 |
BUILDING STANDARDS
DIVISION 25 -- INTEGRATED AUTOMATION
25 00 00 BUILDING AUTOMATION SYSTEMS
- There are three Building Automation Systems (BAS) architectures that shall be acceptable to UIC, defined below as System A, B, or C. Which system to be used shall be job specific and is entirely the choice of the UIC Office for Capital Programs Controls Staff and the Superintendent of Building Maintenance, Bob Deja, (312) 413-2621. These specifications shall be in addition to the requirements for All Systems, listed below.
- System A:
A system comprised entirely of Tridium AX 6xx and 7xx level controllers that serve up the user interface as well as directly control all functions for major equipment (AHUs, central plant etc.) using Tridium I/O expansion modules.
- System B:
A system comprised of Tridium AX 6xx and 7XX level controllers that serve up the user interface and are primarily used as supervisory level controllers to interface to 3rd party field level controllers such as VAV boxes, AHU controllers, chillers etc. Acceptable manufacturers for these field level controllers shall be Alerton, Distech, KMC Open Bacnet, AAM Open Bacnet, and Honeywell Spyder with fully open Bacnet License.
- System C:
A system comprised entirely of Alerton field level and supervisory level controllers, connected to the existing Alerton Envision front end.
- Specific system specification requirements are:
- System A - Tridium:
- Room numbers shown on graphic screens shall be dynamically linked to the description tag of the object in the Tridium database that represents that VAV serving that room.
- Tridium Building automation system license:
- All Tridium controllers shall be provided with a fully open license that follows the format shown below. Where a field is shown as an asterisk "*" it shall be understood to mean that parameter is open to all possible values.
All features shown below shall be included in every Tridium device installed.
- Where a feature below is shown with an expiration or limit as "never" or "none" so shall those parameters be for any license for any Tridium device provided.
feature name="about" owner="UIC" project="UIC"/
feature name="brand" brandId="brand" accept.station.in="*"
accept.station.out="*" accept.wb.in="*" accept.wb.out="*"/
feature name="bacnet" expiration="never" device.limit="none" export="true"
history.limit="none" point.limit="none" schedule.limit="none"/
feature name="email" expiration="never"/
feature name="lonworks" expiration="never" device.limit="28"
history.limit="none" point.limit="none" schedule.limit="none"/
feature name="mstp" expiration="never" port.limit="4"/
feature name="ndio" expiration="never" device.limit="none"
history.limit="none" point.limit="none" schedule.limit="none"/
feature name="niagaraDriver" expiration="never" device.limit="none"
history.limit="none" point.limit="none" schedule.limit="none"/
feature name="obixDriver" expiration="never" device.limit="27" export="true"
foreignDevice.limit="27" foreignHistory.limit="none" foreignPoint.limit="none"
foreignSchedule.limit="none" history.limit="none" point.limit="none"
schedule.limit="none"/
feature name="serial" expiration="never"/
feature name="station" expiration="never"/
feature name="web" expiration="never" ui="true" ui.wb="true"/
- The Tridium device shall come with the most current revision of software released by Tridium.
- A one year warranty shall be provided a part of any TCC contract by the TCC at no extra charge to the University. This warranty shall include all software and labor to implement all Tridium issued revisions and updates for one year from the date of system acceptance by UIC OCP.
- Programmer must be certified in Niagara AX product programming, and must be a resident employee from an office within 50 miles of the job site. Temporarily importing an employee from a further office just to do programming shall be unacceptable, as it will cause warranty coverage issues.
- The user graphics shall be distributed among each building's individual JACE supervisors/controllers, with a central server used primarily for long term trend storage and as a user gateway across campus systems. Each building may have a different approved manufacturers' field controllers as VAVs or fan controllers, etc; however these systems shall be integrated back into a Tridium JACE as a supervisor and web server engine.
- System B: - Tridium as supervisory level with 3rd party field controllers.
- See System A (above) and also All Systems (below) requirements.
- System C: - Alerton only:
- The Alerton Envision central computer will provide the operator with a point of entry to view and store the data that is required for efficient system operation.
- Front End Computer System: The software shall include a real-time multi-user operating system.
- Operator Interface with the system will have as a minimum the following:
- Operator access
- User control over system configuration
- Facility management functions
- Energy management control functions
- Each category of software shall consist of interactive software modules utilizing standard software packages available on the open market and not proprietary to any one equipment provider. Each module shall have an associated priority level and shall execute as determined by the program controller as defined in the real-time operating system.
- The Software shall use English language for each point identification. These shall be full English words with the option to abbreviate at the user's discretion. The system shall accept multiple English language identifiers as well as foreign language identifiers for each point on the system. These shall be known as "User Names". In addition, system formatting shall be provided which shall allow for software grouping of related points.
- The system shall operate on a Format basis, regardless of the manner of hardware configuration in which data is acquired. A system of points shall consist of a logical grouping of data points related to a piece of mechanical
equipment, and energy distribution system, or an architectural area. For example, in some cases it may be desired to display a space temperature with its associated air handling unit, and in other cases to display all space temperatures on a floor or in a building as a single system.
- The Software shall allow such determinations to be made without regard to physical hardware location(s). Likewise, the system shall accommodate future changes of system grouping and operations without field hardware changes.
- User names, point descriptors, and engineering units shall be operator definable on a per point basis. Systems which use fixed vendor-supplied look-up tables are not be acceptable.
- User Control Over Configuration:
- The intent of this standard is to provide a system which shall allow the University to independently do its own modifications to the system.
- It is the intention of the University to have automated and control systems which meet the requirements of BACnet communication according the ASHRAE standard SPC-135A/95 at every level of the device network.
- All controllers performing algorithmic calculations and control of the Air Handling and other primary mechanical equipment shall have BACnet Class 3 performance as a minimum.
- ALL SYSTEMS: The following requirements shall apply to all systems.
- A trunk cable riser diagram showing Digital System Controllers/Security Digital System Controllers/Fire Digital System controllers (DSC/SDSC/FDSC) locations, and all trunk data conductors shall be furnished.
- TCC shall provide all field controller programming tools, network management tools, and any other software that would be used to commission all controllers used in that project. All software provided shall be licensed to UIC, shall be full-featured (not a limited or trial version) and shall not expire, and shall be provided on CD media. At the owner's (UIC-OCP) discretion, upgrades to existing software may be allowed where UIC already owns sufficient copies of the base software.
-
The programming tool for field controller must be object oriented and shall use a graphical interface. This tool shall be self-documenting into either ACAD or VISIO format.
- The building automation system shall be web based with the
following features as minimum:
- System shall provide real-time navigation through the system
and auto
listing of all BACnet devices on the network and their objects.
- System shall provide view and edit operations of most objects
(I/O,
variables, schedules, trend) including Auto/Manual, set point,
descriptions, etc.
- Users shall be able to view and acknowledge active alarms.
- Alarm notification can be e-mailed.
- System shall provide the same level of security as the
on-site operator's terminal.
- System shall allow unlimited concurrent users.
- All
materials and equipment used shall be standard components, regularly
manufactured for this or other systems and not custom designed. All
systems and components shall have been thoroughly tested and proven in
actual use for at least two years.
- The sequence of operation for every system shall be included in the Building Automation System on the same screen showing that system graphic. There shall be a sub-link on the screen to direct all users to such sequence of operation.
- Each Graphic screen shall have a text screen associated with it, and the user will be able to switch back and forth between each unit’s graphic and text screen via a hyperlink button.
- All floor plan layouts shall be included in the building automation system. Access to the floor plan shall be through a sub link on the same screen showing the graphics of the HVAC serving that space.
- Building Automation Systems (BAS) performance requirements shall include the following applications:
- Heating,
Ventilating and Air Conditioning Monitoring, Equipment and Lighting
Control
- Energy
Management Routines
- Future Fire
Alarm connectivity through existing BAS
- Miscellaneous
Equipment Monitoring
- A
trunk cable riser diagram showing Digital System Controllers/Security
Digital System Controllers/Fire Digital System controllers
(DSC/SDSC/FDSC) locations, and all trunk data conductors shall be
furnished.
- Company shall provide programming editing tool for every project, for all databases and for programming field controllers and program shall be self-documenting by printout into either VISIO or ACAD format.
- The programming tool for field controller must be object oriented and should use a graphical interface.
- All
BACnet devices shall include all hardware and software necessary to
integrate the controls with the existing BACnet over Ethernet or IP
network and meet the systems functional specification.
- Any
BACnet device that exists on a common BACnet inter-network must have a
unique address, referred to as its Device Instance. The Chief Plant
Operating Engineers Office shall establish the Device Instance
numbering system.
- The
BAS shall be a computer based distribution system that shall monitor
life safety, mechanical and electrical equipment status and have the
capability of controlling certain mechanical, electrical and life
safety system components. The architecture of the system shall be a
distributed one in which the monitor/control function responsibility is
located as close as possible to the monitored/controlled variable. This
results in several levels of processing which can stand alone should
the communication be lost to the next higher level of processing.
- Equipment
Control will be provided by programmable or application specific
Controllers. All algorithms required for standalone operation of each
control loop will be contained within the unique board. The controlled
equipment will maintain its set points and logic regardless of
centralized network communications.
- All enclosed relays used with an indicating LED (like R.I.B’s) shall use a printed label describing its functional state, i.e. “ON to run” or “ON for alarm”.
- BAS shall monitor/control all the points and functions as
listed below.
- Inputs
monitored or alarmed and output control functions.
- Digital input
indication signals from contacts associated with on-off,
off-normal, normal or other indications initiated by making or breaking
of the contacts.
- Digital output
signals which shall be two state control outputs, except
as noted, e.g., on-off, open-close, start/stop. Momentary or a
maintained state shall be noted as required.
- Analog I/O
signals which are continuously variable.
- The schedule
shall include calculations from software of functions
monitored, e.g., BTU, kilowatts, etc., if requested by the University.
- The schedule
shall include totalization of variables within the
software. This shall include totalization program requirements for
on-line assignments.
- The
system shall be modular to allow change of function and operation in
the field by plug-in module equipment and permit software change to
expand the system capacity on full on-line basis.
- The
system shall include isolation, shielding, or filtering to eliminate
interference from all external sources including, but not limited to
radio signals, power conductors, etc.
- Networking:
- Each control
unit shall be capable of sharing point information with
other such units, such that control sequences or control loops executed
at one control unit may receive input signals from sensors connected to
other units within the network. If the network communication link fails
or the originating control unit malfunctions, the control loop shall
continue to function using the last value received from the failed
control unit.
At no point in any control system is the campus ethernet network to be utilized as an integral component of the control system - the control system shall be designed to function normally per the sequence of operation without any campus ethernet network present. Where a Tridium system is used, a BACnet MSTP network (separate from any other MACnet MSTP network that connects to other field controllers) shall be run to every JACE controller, specifically for passing system data between controllers. Where an Alerton system is used, dedicated point-to-point ethernet or fieldbus cabling shall be used to connect supervisory level controllers, separate from other fieldbus networks. When using extra network cabling to pass critical data between controllers on a dedicated (non-campus) network is not feasible, other arrangements may be acceptable at UIC-OCP's discretion, like adding redundant sensors or using failsafe control logic.
- Failure of one
control unit shall have no other effect upon any of the other units in
the network.
- The
following is a list of manufacturers of materials and equipment that
are known to have product that is Native BACnet at all levels of device
communications. Only these manufacturers are considered acceptable.
Manufacturers advocating gateways at different levels of their product
line are not acceptable. Gateways and alternative methods of network
communication are only considered acceptable when provided by the
manufacturer of primary plant systems such as Variable Frequency
Drives, Boilers, Packed Rooftop Equipment, Chillers, etc.
MATERIAL OR
EQUIPMENT |
|
MANUFACTURER |
Native BACnet
Temperature Control Systems |
|
Tridium,
Distech, KMC |
- Each Control Panel shall be capable of independently
performing the following routines as a minimum:
- System graphic
- System on/off indication
- System day/night mode
- Supply fan on/off indication
- Return fan on/off indication
- Heating coil pump on/off indication
- Outside air temperature indication
- Mixed air temperature indication
- Fan discharge air temperature indication
- Fan discharge temperature control point adjustment
- Supply static pressure indication
- Supply static pressure control point adjustment
- Humidity sensor
- Enthalpy sensor
- System on/off auto switch position.
- System day/night/auto switch position.
- Supply fan on/off switch position.
- Return fan on/off/auto switch position.
- Heating coil pump on/off switch position.
- Time of day scheduling.
- Start/stop time optimization.
- Peak demand limiting.
- Duty cycling (temperature and/or time based).
- Enthalpy optimization.
- Supply air reset.
- Chilled water reset.
- Hot water reset based on outdoor air temperature.
- Event initiated programs.
- Trending
- The Control Panel shall support the creation, modification or removal of control algorithms while operating.
- The Control Panel shall allow custom control algorithms to be
created:
- Locally within the Control Panel.
- Centrally within the front end computer and downloaded.
- By a personal computer (IBM compatible) and downloaded.
- User Control Over Configuration:
- The intent of
this standard is to provide a system which shall allow
the University to independently do its own modifications to the system.
- All changes
shall be done utilizing standard procedures and must be
capable of being done while the system is on-line and operational. To
aid an operator, intuitive operator interfaces shall be employed. The
operator shall be required to simply click on the set-point, logical
point or other controlled parameter to modify the system.
- The system
shall have the minimum capability to allow the University to do the
following:
- Add and delete
points.
- Modify any
point parameter.
- Change, add or
delete English language descriptors.
- Change, add or
delete engineering units.
- Change, add or
delete points in start/stop programs, trend logs, etc.
- Select analog
alarm limits.
- Adjust analog
differentials.
- Create custom
relationships between points.
- The BAS
software shall support an unlimited number of nodes on the
communication network.
- Once the
hardware terminal devices are installed, the operator shall be
able to modify the system software to accommodate the new or
reconfigured devices.
- It shall be
possible to limit the capabilities of any console on the system.
- It shall be
possible to further assign on a per point basis the ability
to command, display or alarm a point at a specific workstation.
- Provision for facilities management functions shall be
provided as a minimum.
- Provision
for Energy Management Control Functions shall be provided as a minimum
for the purpose of optimizing energy consumption while maintaining
occupant comfort.
- Communication Software:
- The system shall
include software for communication between all
systems. The capabilities of this software shall include program to
program communication, network virtual terminal capability, file
transfer, remote command/batch file submission and execution, remote
resource access, downline system loading, downline task loading, and
upline dumping.
- The software
shall be consistent with ASHRAE Standard 135 and support
the required BACnet system functionality as defined in the Standard.
- Digital Systems Controller (DSC):
- The units shall
maintain the programming and algorithms necessary to
control independent mechanical systems. The Digital System Controller
shall communicate over a local LAN connected to the System LAN at the
individual control panels.
- These units
shall connect directly to control unit through a local area
network, providing additional local digital point capacity. All control
programs shall reside within the associated control unit.
- Digital System
Network (DSN):
- Network
Controllers shall be stand-alone, multi-tasking, multi-user,
real-time digital control processors consisting of modular hardware
with plug-in enclosed processors, communication controllers, power
supplies and input/output point modules.
- Each Controller
shall have sufficient memory to support its own operating system and
databases, including:
- BAS Control
processes
- Energy
management applications
- Alarm
management applications including custom alarm messages for each level
alarm for each point in the system.
- Historical/trend
data for points specified
- Maintenance
support applications
- Custom processes
- Operator I/O
- Dial-up
communications
- Each DDC
Controller shall support any combination of industry standard inputs
and outputs.
- As indicated in
the point I/O schedule, the operator shall have the
ability to manually override automatic or centrally executed commands
at the DDC Controller via local, point discrete, on-board hand/off/auto
operator override switches for digital control type points. Switches shall
be mounted either within the DDC Controllers
key-accessed enclosure, or externally mounted with each switch keyed to
prevent unauthorized overrides.
Alternately, external relays with HOA function can be used, provided they are mounted in an orderly fashion inside aforementioned locking control panels and are wired back into controller inputs to show all relay HOA switch positions.
- DDC Controllers
shall provide local LED status indication for each
digital input and output for constant, up-to-date verification of all
point conditions without the need for an operator I/O device. Status
indication shall be visible without opening the panel door.
- Each DDC
Controller shall continuously perform self-diagnostics,
communication diagnosis and diagnosis of all panel components. The DDC
Controller shall provide both local and remote annunciation of any
detected component failures, low battery conditions or repeated failure
to establish communication.
- Isolation shall
be provided at all peer-to-peer network terminations,
as well as all field point terminations to suppress induced voltage
transients consistent with IEEE Standards 587-1980, or latest edition.
- In the event of
the loss of normal power, there shall be an orderly
shutdown of all DDC Controllers to prevent the loss of database or
operating system software. Non-volatile memory shall be incorporated
for all critical controller configuration data and battery backup shall
be provided to support the real-time clock and all volatile memory for
a minimum of 72 hours.
- Upon
restoration of normal power, the DDC Controller shall automatically
resume full operation without manual intervention.
- Should DDC
Controller memory be lost for any reason, the user shall
have the capability of reloading the DDC Controller via the local port,
via telephone line dial-in or from a network workstation PC.
- Data Trunk:
- Transmission Network:
- The system shall use an intelligent distributed communication network.
- Transmission
- Network communications shall be of the ASHRAE 135 Standard
- Definitions:
The following abbreviations, acronyms and definitions are used in
addition to those details found elsewhere in Contract Documents.
| Actuator: |
Control device
to provide motion of valve or damper in response to control signal. |
| AI: |
Analog Input |
| AO: |
Analog Output |
| Analog: |
Continuously
variable state over stated range of values |
| ATC: |
Automatic
Temperature Control |
| Auto-Tune: |
Software
routine used to adjust tuning parameters based on historical data. |
| BAS: |
Building
Automation System |
| BCU: |
Building
Control Unit |
| CAV: |
Constant Air
Volume |
| CGS: |
Color Graphic
Software |
| DDC: |
Direct Digital
Control |
| DDCP: |
Direct Digital
Control Panel |
| Discrete: |
Binary or
digital state |
| DI: |
Discrete Input |
| DO: |
Discrete Output |
| EMCS: |
Energy
Management and Control System (Same as BAS) |
| FC: |
Fail Closed
position of control device or actuator. Device moves to closed position
on loss of control signal or energy source. |
| FMS: |
Facility
Management System linking two or more BAS |
| FO: |
Fail Open
position of control device or actuator. Device moves to open position
on loss of control signal or energy source. |
| HCP: |
Host Control
Panel |
| HOA: |
Hand-Off-Auto |
| I/P: |
Current to
pneumatic transducer |
| Instrument: |
Device used for
sensing input parameters or used for actuation |
| LAN: |
Local Area
Network |
| LCD: |
Liquid Crystal
Display |
| LCP: |
Local Control
Processor |
| Modulating: |
Movement of a
control device through an entire range of values proportional to
infinitely variable input values. |
| Motorized: |
Control device
with actuator. |
| NC: |
Normally Closed
position of switch after control signal is removed or
normally closed position of manually operated valves or dampers. |
| NCP: |
Network Control
Processor |
| NO: |
Normally Open
position of switch after control signal is removed or
normally open position of manually operated valves or dampers. |
| Node: |
DDCP, user
workstation, or other control device connected to communication's
network. |
| Operator: |
Same as
actuator. |
| PC: |
Personal
Computer |
| Peer-to-Peer: |
Mode
of communication between controllers in which each device connected to
network has equal status and each shares its database values with all
other devices connected to network. |
| P: |
Proportional
control, control mode with continuous linear relationship
between observed input signal and final controlled output element. |
| PHP: |
Public Host
Protocol |
| PI: |
Proportional -
Integral control, control mode with continuous
proportional output plus additional change in output based on both
amount and duration of change in controlled variable (Reset control). |
| PID: |
Proportional -
Integral - Derivative control, control mode with
continuous correction of final controlled output element versus input
signal based on proportional error, its time history (reset), and rate
at which its changing (derivative). |
| Point: |
Analog or
discrete instrument with addressable database value. |
| PUC: |
Programmable
Unitary Controller |
| PUP: |
Public Unitary
Protocol |
| RAM: |
Random Access
Memory |
| RCU: |
Remote Control
Unit |
| Self-Tune: |
Same as
Auto-Tune |
| Solenoid: |
Electric
two-position actuator. |
| TCC: |
Temperature
Control Contractor (Same as Control Contractor) |
| TCP: |
Temperature
Control Panel |
| VAV: |
Variable Air
Volume |
- The
HVAC temperature control hardware will be native BACnet. Native BACnet
means that the database objects in the controller can be seen by other
BACnet systems, and data can be exchanged between other BACnet devices
without the need for a gateway.
- Internet Protocol Address (IP) will be assigned by the University at the building location.
- All Building Automation Systems must provide for remote communications to the Central Operations Office of the Operating Engineer on both the East and West Campuses.
- All LON wiring must be 22 AWG UTP level 4.
- All BACnet wiring must be shielded 18 AWG level 4.
- Acceptable Control Contractors:
- Tridium
- Alerton Technologies
- Distech
- KMC
- Systems Description:
- Control system
shall be direct digital control (DDC).
- Control to be
based on BAS architecture consisting of communication
network, user workstations, modular designed DDCPs with all points
addressable and modifiable from user workstations or from master DDCP
user interface panels. BAS shall be fully stand-alone and shall
communicate via BACnet/Ethernet/Internet communications protocol.
System components shall be fully BACnet/Ethernet/Internet compliant
without the use of gateways. System must be able to communicate with
the main platform at the University of Illinois at Chicago
via Internet Protocol (IP) Address, assigned by the University at the
building location.
- System shall
support user workstations as specified and shall be
capable of additional workstations, limited only by systems maximum
node capacity.
- System
intelligence shall be such that user workstation(s) can be used
for programming controls, performing analysis on filed data, perform
trending of user defined inputs, generating maintenance and operation
reports, providing permanent storage for programs and data, and the
ability to connect to the Internet.
- Safety devices
shall function in both auto and hand modes on starter.
- Recommended instrument and control conductor color code shall
be as follows:
Type
|
Color |
120 VAC control
signal
|
Red |
120 VAC
instrument line power
|
Black |
120 VAC
instrument line neutral
|
White |
24 VAC control
signal
|
Yellow |
24 VAC
instrument line power
|
Brown |
24 VAC
instrument line neutral
|
Orange |
Grounds
|
Green |
24 + VDC
instrument signal
|
Black |
24 - VDC
instrument signal
|
White
or clear |
RTD V+
|
Black |
RTD V-
|
White |
RTD compensation
|
Red |
- Electric
signal cables from electronic transmitters to receivers and from
controllers to final control elements shall be continuously shielded.
Shields shall be grounded at power source end only and floated at the
other end.
- BAS Network Communication Cable:
- BAS network
communication cable shall not be spliced.
25 11 00 INTEGRATED AUTOMATION NETWORK DEVICES
- All newly installed BACnet devices shall be installed on two non-firewalled network segments, one for each campus, reserved solely for these devices. No NAT firewalls are to be used on this network. Additional network segments may be added in the future as needed.
- Integrating devices from multiple vendors requires careful administration of various configuration and management data. Critical vendor device configuration information includes:
- IP number
- IP delegation, routing and switch management are maintained by the Academic Computing and Communications Center (ACCC). IP numbers shall be assigned and registered in the UIC DNS by a REACH representative (currently Bob Deja, as of 03/10/2008.)
- Device Instance number
- Device instance numbers are BACnet native identifiers. Instance numbers must be confirmed with the Physical Plant REACH representative prior to device installation and must be registered in the UIC BACnet database upon registration of the IP number used for said device. UIC Instance numbers shall conform to the following format:
XXXYYYY
where: XXX = UIC building number
YYYY = unique numeric identifier within the designated building.
The resulting numeric string constitutes a campus-wide unique identifier, in order to prevent network device conflicts.
- Virtual Network Number
- Virtual network numbers are BACnet designators which segregate BACnet traffic between different vendor devices. Virtual network numbers must be confirmed with the Physical Plant REACH representative prior to device installation and must be registered in the UIC BACnet database upon registration of the IP number used for said device. Each vendor will have sole use of delegated numbers, to prevent network segment conflicts.
- UIC BACnet Database Storage
- The UIC BACnet database tables store all necessary information critical to the administration of network configuration and management data. ACCC shall maintain these tables and provide a web-based interface to insert, update, and retrieve all BACnet data. All IP numbers used must be registered in the UIC DNS as well as the UIC BACnet database tables. Table information includes:
- IP number
- Device Instance number
- Virtual Network number
- Vendor name
- Device type (Server, BBMD, OWS, etc.)
- Building number
- Room number
- update id (auto-generated netid of person who updated field)
- timestamp (auto-generated upon database insertion/update)
25 13 00 INTEGRATED AUTOMATION CONTROL AND MONITORING
NETWORKS
- Direct
Digital Control Panels (DDCP's) shall be microprocessor based, field
programmable controllers, capable of performing control and energy
management functions, and shall be UL listed as Signaling Systems. Each
DDCP shall include its own microprocessor, power supply, input/output
modules, and termination modules as required to perform its intended
function.
- DDCP
shall receive discrete electrical or analog electronic field input
signals, convert signals for use by controller, perform control
sequences, convert controller information into output signals, and
provide control output signals to actuators and field control device.
All inputs and outputs, including communication connections, shall be
electrically or optically isolated from controller.
- DDCP
with analog input modules shall be capable of accepting any form of
linear or non-linear voltage (0-5 VDC or 0-10 VDC), current (4-20 mA)
or resistive input (0-1000 ohm).
- DDCP
with discrete input modules shall be capable of accepting discrete
inputs from any device with isolated, dry-type contacts (no grounds or
no voltage) of either normally open (NO) or normally closed (NC)
configuration.
- Input modules shall be capable of interfacing with pulsed
output type sensors.
- DDCP
shall have capability to scale, offset, and display proper analog value
without field hardware modification. DDCP shall convert analog input
signals to digital values (A/D conversion) and convert digital values
to analog outputs (D/A conversion) for modulating control purposes.
- Failsafe
operation shall be provided such that BAS failures result in immediate
return to local control. If the DDCP uses database values from other
DDCP and the communication network fails or malfunctions, control loop
outputs shall continue to function using last value received from BAS.
- DDCP
shall have ability to interface and communicate with Host Control Panel
(HCP) through a dedicated network. DDCP shall be fully operable from
and have all points and functions available to centrally alarm at any
DDCP or PC workstation connected to a BAS network.
- Three
types of DDCP's are allowed, Building Control Units (BCU's), Remote
Control Units (RCU's), and Application Specific Controllers (ASC's).
- BCU's
are defined as having capabilities of direct connection to high speed
Local Area Network (LAN) (greater than 500 kilobaud), serve as
communications hub for other BCU's on slower speed LAN, and have
sufficient processor capabilities and RAM to implement all types of
custom software applications. BCU's shall have serial type input/output
(I/O) ports to directly support operator workstations (portable PCs),
standard ASCII dumb terminals, modems, and all types of printers.
- BCU's
shall have uninterrupted real time clocks capable of time of day, week,
and year information to the system as needed to perform software
functions. Clock shall be programmed to reset twice a year to allow for
Daylight Savings Time. Clocks in multiple BCU's shall be synchronized
automatically to match designated BCU or workstation. Accuracy shall be
within 1 second per day minimum.
- BCU
batteries shall maintain all volatile memory and real time clocks for a
period of at least 72 hours during power failure. Batteries shall be
maintenance free and have minimum life of 2 years. When power has been
restored, the following shall occur automatically:
- Orderly startup
of all controlled equipment (user defined).
- Continuation of
all control algorithms.
- Data base
revision.
- Log times of
power interruption and restoration.
- Battery
recharging.
- RCU's
are defined as being the same as BCU's but without high-speed LAN
capabilities or I/O ports. RCU's shall communicate with BCU's and other
RCU's via low/medium speed network or direct serial or parallel data
bus interface.
- ASC's
are defined as having standard software burned into EPROM, set points
in EEPROM or RAM maintained by battery, and are designed to handle
specific types of control sequences. ASC's shall be capable of
communicating to BAS network via low/medium speed network connected to
BCU's.
- All
software and hardware to be covered by site license for a minimum of 30
users. Adding to or modification of the basic system should not require
additional licenses.
- BCU/RCU Software shall contain:
- Program
modules for performing energy management control functions such as time
of day change of database values (programmed start/stop, temperature
setbacks, etc.), supply air temperature reset based on space load
demand, economizer control, optimum start/stop based on current indoor
and outdoor psychometrics, duty cycling and client tailored programs
required for special applications such as VAV fan matching and supply
fan control, enthalpy control, intermediate season or "dead band" control, totalizing, and holiday programming.
- Manufacturer's
standard operating system for real time control of
system interactions, including database information requests/transfers
by system hardware or by operators. Operating system shall also have
the following additional capabilities (given operator has appropriate
security access level):
- Display any
database (point) value including measured values,
controlled variables, set points, gain factors, and any other
adjustable parameter.
- Change or
override any database value.
- Error
detection, correction, re-transmission of database values, arithmetic
or logical faults.
- Alarm reporting
including sending alarms to remote workstations on network or by modem.
- Alarm buffer to
retain all alarms in order of importance without losing any alarms.
- Creating and
displaying historical trend logging any value limited only by available
memory.
- Create new
variable database values (soft points) based on arithmetic
calculation (including summation or totalizing) on other database
values.
- Add new
hardware points without overall BAS shutdown.
- All
hardware/software to update database in less than 1 second for
fast-acting control loops such as pressure control, air or water volume
control, and air handling unit temperature control, or 10 seconds or
less for all other control loops.
- Graphics to be generated shall include, but not be limited
to:
- Site Plans,
including each building, building name, and status of all exterior
points such as lighting, etc.
- Overall
building plan of each building. Indicate location of mechanical rooms
and areas served by each air handling unit.
- Voltage and
current values shall be displayed for all motors 50 HP and
above. Each shall be displayed next to the motor graphic on the display
screens.
- Schematic type
graphics for:
- Each air
handling system
- Supply fan
control loop
- Cooling coil
control loop
- Heating coil
control loop
- Humidifier
control loop
- Damper control
loops
- Steam system
showing all components
- Each hot water
system showing all components.
25 30 00 INTEGRATED AUTOMATION INSTRUMENTATION AND TERMINAL
DEVICES
- Accuracy of devices shall be ± 1% of scale with
adjustable offset unless otherwise specified.
- Wall mounted space thermostat enclosure shall have concealed
sensing element and exposed set point adjustment.
- Unless otherwise stated, space thermostat covers shall be
brushed aluminum or brushed nickel.
- Temperature Low Limit Switches (Freezestats):
- Electric 2
position type with temperature sensing element and manual
reset. Controls shall be capable of opening circuit if any one foot
length of sensing element is subject to temperature below setting.
- Sensing element
shall not be less than one lineal foot per square foot
of coil surface areas. Temperature switch set point is 38°F.
- Where multiple
switches are required, each switch shall have a separate
point names in the BAS. Each alarm in BAS shall indicate which
temperature low limit has opened or tripped.
- Pressure Differential Switches (Air Systems):
- Pressure
differential switches for air systems shall have pressure rating of at
least 1-1/2 times the systems pressure.
- Pressure Differential Switches (Water Systems):
- Pressure
differential switches for water systems shall be rated for 1-1/2 times
system pressure. Chilled water pressure differential switches shall be
provided with totally sealed vapor tight switch enclosure. Differential
pressure switches to have 3-valve manifold for servicing.
- Level Switches (Ultrasonic Gap Sensor):
- Radio Frequency
(RF) type point level probe with stainless steel probe
and DPDT snap action relay contacts to meet intended use. Probe shall
have a machined gap in the probe to sense presence or absence of water
or other fluid. Probe length shall be determined by application.
- Analog
Electronic Instrumentation: The following shall be standard
off-the-shelf, commercially available and applicable for use with
electronic control/monitoring systems.
- Space
Temperature Sensors
- Duct Mounted,
Insertion or outside Temperature Sensors
- Direct
Insertion Temperature Sensors
- RTD Temperature
Transmitters
- Space Humidity
Sensors/Transmitters
- Duct Mounted
Humidity Sensors/Transmitters
- Ducted Air
System Static Pressure and Differential Pressure (Velocity)
Transmitters
- Pressure/Differential
Pressure Transmitter
- Vortex
Flowmeter/Transmitter (Steam)
- Capacitance
Type Level Transmitter
- Pressure (E-P)
Transducers
- Carbon Monoxide
Monitor
25 35 16 INTEGRATED AUTOMATION SENSORS AND CONTROLS
- Control Instruments
- Thermostat
- Temperature Sensors
- Valves / Actuators
- Dampers / Actuators
- Humidity Sensors
- Control Panels / Transformers and Wiring
- Electronic Building Network Controllers
- Networked Modular I/O and Unitary Controllers
- Local and Remote Browser / Operator Work Station
- Building Site Server / Firewall Description
- Hardware
- BAW/OWS Issues
- Water Flow Meters (Magnetic)
- Differential Pressure Transmitter (Liquid)
- Gas Meter
- Demand Control CO2
- Air Flow Measuring
- Gas Monitoring
- Lighting Control
- Security Control
- Miscellaneous Control Equipment Wiring
- Programming/Graphics
- Programming will combine the simplicity of graphical programming with the precision and efficiency of line-oriented Java script programming. It must deliver a library of math, logic and control blocks that the programmer can drag and drop onto the screen to graphically model the control strategy for a piece of HVAC equipment. These control strategies must provide excellent sequence documentation and are reusable, eliminating the need to recreate them for every project.
- NOTE: The BAS system must have:
- A built-in web server and Internet interface.
- XML formatted data over HTTP.
- FOX over IP or ASHRAE BACnet/IP protocol over Ethernet cabling.
- Microsoft Windows XP or 2000 Professional Operating Systems compatibility.
- IT-friendly connectivity, firewall compatible.
-
All points shall be trendable.
-
The successful bidder shall provide graphs of trend logs of all points specified by the A/E on the point list for every project. It is the intention of the University to have trend logs periodically (i.e., every 15 minutes). The successful bidder shall prove to the university through the trend logs that all devices are working properly and smoothly (i.e., no hunting of valves or dampers will be allowed).
- There shall be an option for Internet users to edit the frequency of time for the trend log table.
- There shall be a sub-link which directs to a page where one can overlap the different graphs at one time at the same scale.
-
The BAS contractor will display all dynamic color graphics as required by owner.
- All color graphic floor plan (project's CADD/Auto CAD drawings transported) displays and system schematics for each piece of mechanical equipment, including air-handling units, chilled water systems and hot water systems will be provided to optimize the system performance analysis and speed alarm recognition. The sequence of control for each piece of mechanical equipment shown on a graphic must also be included as an overlay on that screen. This will allow the operator to review the sequence of control on the graphical screen pertaining to mechanical equipment shown. All software engineering required to construct the graphics to be included under this contract.
- System operator security/penetration: The system operator's security clearance level will allow the user to access the various system schematics and floor plans, based upon the owner's appointed security level given to that user.
- Dynamic data displays: Dynamic temperature valves, humidity valves, flow valves and status conditions shall be shown in their actual respective locations and shall automatically update to represent current conditions without operator intervention.
- Graphics' colors pertaining to on/off status will be "green" for on and "red" for off conditions.
- Dynamic objects shall include analog and binary values, dynamic text and static text.
- Basic design considerations for building temperature control include the following:
- The use of hydronic heating is preferred.
- Direct radiation in rooms should be provided with wall thermostatic control.
- Room thermostats shall control all heating and cooling in the room.
- A diagram of the temperature control system and a sequence of operations prepared by the Contractor and mounted under glass shall be installed in the mechanical equipment room for each project.
- All HVAC air-handling units must be provided with a manually adjustable freezestats.
- Winter-summer changeover switches and damper control switches must have manual override provisions incorporated in the temperature control systems.
- Provide a high limit humidistat in systems with humidifiers.
- When cooling is introduced in the system, it is preferred (if reciprocating type compressors are used) that the compressor operates on suction pressure control to give approximately constant suction temperature, and a relatively constant apparatus dew point. A solenoid valve in the liquid line at the expansion valve, operated by room or return air humidistat can be used, and together with the reheat coils and controls maintain predetermined room temperature and humidity.
- Automatic Dampers
- Each damper section shall have an individual operator. No linkages shall be installed between dampers to transfer operator power. Manufacturer's catalog information shall be de-rated 50% for application to provide positioning of the dampers. Damper operators shall not be of the swing mounting type. They should be mounted outside the air stream where possible, especially in outside air applications. Pneumatic control lines, where they penetrate outside air ducts, shall include dehydrator units. Outside air and return or relief dampers that are automatically controlled shall be of the minimum leakage type. Quality of dampers shall be specified, including air leakage at 3/4 inch static pressure when the damper is in the closed position. Provide neoprene edges and tips on blades.
-
Electronic Control valves and Dampers
- All control valves and dampers shall be electronic modulating.
- They shall all be "proportional" and shall provide feedback to the BAS.
25 55 00 INTEGRATED AUTOMATION CONTROL OF HVAC
- Provide a Sequence of Operations for new building Systems as
approved by the User.
- Provide Central HVAC Systems Display as applicable:
- System graphic
- System on/off
indication
- System
day/night mode
- Supply fan
on/off indication
- Return fan
on/off indication
- Heating coil
pump on/off indication
- Outside air
temperature indication
- Mixed air
temperature indication
- Fan discharge
air temperature indication
- Fan discharge
temperature control point adjustment
- Supply static
pressure indication
- Supply static
pressure control point adjustment
- Humidity sensor
- Enthalpy sensor
- System on/off
auto switch position.
- System
day/night/auto switch position
- Supply fan
on/off switch position.
- Return fan
on/off/auto switch position.
- Heating coil
pump on/off switch position.
25 36 13 INTEGRATED AUTOMATION POWER METERS
- All new buildings constructed at UIC shall have a new networked utility (BTU) metering system installed and integrated with the campus Energy Management System as owned and maintained by the Utilities department. All projects at UIC that involve HVAC renovations or improvements with a projected budget of over $125,000 shall consult with the Director of Utilities about the possible need for new networked metering in that building.
- BTU metering system shall consist of: flow metering heads and temperature sensors for Chilled Water and High Temperature Hot Water service from the plant, and steam volume metering heads, temperature and pressure sensors along with condensate return volume where used. Metering heads and all pressure and temperature sensors shall be directly connected to a local Btu meter. Installation of all metering components shall fully comply with that component manufacturer’s recommended installation practices, especially where lengths of straight pipe and component fastening are concerned.
- BTU meter shall include these features at a minimum:
- Input resolution of .0015% of full scale, 16 bit A/D. Input impedance > 1 Mohm.
- A measurement rate of 10x per second on all inputs.
- All inputs shall be configurable to read any combination of 4-20mA, J K T E N S B Thermocouples, and RTDs. RTDs shall have a base accuracy of 0.2% or 0.5 °C (1 °F) and resolution of 0.1 °C.
- User programmable recording rates, starting at 10 samples per second.
- Ability to store all data at the meter in NVRAM collected from 12 channels over a 7 day period at 1 sample per second.
- Built-in Ethernet port that allows all data to be sent to the Utilities Energy Management System via MODbus/TCP or BACnet/TCP protocols.
- Built-in local screen with the ability to show live or archived data from any input channel.
- All meter features shall be fully programmable via the built-in screen and buttons on the meter. No external software shall be needed to set up or program any meter features.
- Meters shall operate accurately in environments from 0 °C to 50 °C, 10% to 80% RH (non-condensing).
- BTU meters shall be UL rated and meet requirements of EN61010-1.
- BTU meter shall communicate to flow metering heads via 4-20mA loop or MODbus protocol over RS485.
- Flow metering heads for Chilled Water (CHW) shall be ABB WaterMaster electromagnetic flow meters or Flexim Ultrasonic flowmeters (or 100% equivalent).
- Meters shall meet or exceed OIML R49-1 standard.
- Meter housing shall meet NEMA 4X or IP 65 at a minimum.
- Meters shall operate accurately in environments from -20 °C to 70 °C, 0% to 100% RH.
- Meter shall output its signal via 4-20mA loop or MODbus protocol over RS485.
- Flow metering heads for High Temperature Hot Water (HTHW) shall be Flexim Ultrasonic flowmeters (or 100% equivalent).
- Flow meter shall be capable of achieving accuracy within +/- 0.5% of the flow reading +/- 0.1 m/s with a field calibration.
- Meter housing shall meet NEMA 4X or IP 65 at a minimum.
- Repeatability shall be 0.15% of reading +/- 0.1 m/s.
- Response time shall be 1 second or less; the measuring cycle shall be adjustable from 100 to 1000 Hz.
- Flow metering heads for Steam measurements shall be Sierra Instruments series 240 ultrasonic (or 100% equivalent).
- Mass Flowrate shall be accurate to +/- 1.5% over a 30:1 range from 50 to 100% of the pressure transducer’s full scale.
- Volumetric flow rate shall be accurate to +/- 1% of rate over a 30:1 range.
- Temperature accuracy shall be +/- 1 °C.
- Pressure shall be accurate to 0.4% of transducer full scale.
- Density shall be accurate to 0.5% of reading from 50 to 100% of transducer’s full scale.
- Response time shall be adjustable from 1 to 100 seconds.
- Meter shall have an alphanumeric display and feature a NEMA 4X explosion-proof housing.
- Meter shall feature 4-20mA for output signals; no pulse outputs are allowed.
- Meter shall be capable of accurate operation in an environment ranging from -5° F to 140° F; 0-98% RH (non-condensing).
- All temperature sensors used in metering shall consist of a balanced matched pair per application; sensors shall have an NIST traceable accuracy.
- In installations where both the CHW and HTHW metering heads are to be provided by FLEXIM, then a FLEXIM BTU meter shall also be used.
- Electrical meters shall be EMON 3000 series with BACnet/IP communication . Each meter shall communicate with and send data to the existing campus TRIDIUM server (with Energy Analytics Software). Trend / History polling intervals shall be set up for 15 minutes. Failure to use a 15 minute interval skews the data. Real Voltage, Current, Demand and Consumption data shall be provided at a minimum.
- Manufacturer site start-up shall be provided along with meter. Electrical meter provider shall fully commission each device and provide a report to the Director of Utilities at UIC confirming meter accuracy as installed. Manufacturer factory calibration certification shall not be used as a substitute for this report.
- In new construction, a meter shall be provided and installed for each of these: Total building power, HVAC / MCC power used, Lighting power used, and general building power used (i.e., outlets).
- Meter shall come in a NEMA 12/13 housing.
|