HVAC SYSTEMS In modern buildings the heating, ventilation, and air conditioning (HVAC) system is designed and installed to maintain a comfortable environment for the occupants. This includes maintaining comfortable temperatures and relative humidity levels uniformly throughout the office space, providing perceptible air movement without drafts, eliminating stale air, and providing adequate quantities of outside air in order to prevent the buildup of air pollutants. In a typical HVAC system, the air is provided by a supply fan or air handling unit (AHU) which receives air from from outside the building, and air recirculated from the office space. The outside and return air are mixed in the mixing chambert, filtered, heated or cooled, and delivered to occupied areas through sheet metal ducts. These sheet metal ducts discharge the air into the office space, usually through supply air diffusers located on the drop ceiling. MIXING OUTSIDE AND RECIRCULATED AIR The outside air is drawn through a duct which is usually located on the roof of the building, and the return air is delivered to the supply fan by the return or exhaust fan. The return air fan exhausts air from the office through return air vents into the space above the drop ceiling (called the return air plenum). This return air then goes through a return duct to the fan room. The return air can then be exhausted to the outside and/or recirculated. The return air moving through the plenum above the drop ceiling often comes in contact with pollutant sources, including fibrous glass insulation on the ducts or in sprayed on fire proofing, asbestos insulation on pipes or in fire proofing, and chemicals off-gassing from the ceiling tiles. (See the CWA fact sheet "Office Indoor Air Quality".) The amounts of return air and outside air mixed together is controlled by dampers in the return and outside air ducts. Each damper can move to any position from fully closed to fully open. The return air, exhaust air, and outside air dampers all work together so that when the outside air damper is fully open, the return air damper is closed and the exhaust air damper is open. On the other hand, when the outside air damper is closed, the return air damper is fully open and the exhaust damper is closed. In this mode the ventilation system would be entirely recirculating office air. Indoor air quality problems usually occur when the outside air dampers are not open enough to provide adequate amounts of outside air. The American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) normally recommends that a ventilation system should deliver at least 15 to 20 cubic feet per minute (cfm) of outside air per occupant. AIR CONDITIONING (COOLING) During the summer months, air is passed through water-filled coils which look like the radiator in your car. This is called a cooling coil. The water flowing through the coil is around 40 ° F. The ventilation air does not contact the water, only the cold metal surface of the coil. This is enough to cool the air to 60 ° F before it is sent to the offices. The cold water is produced in the building by refrigeration units called chillers, and pumped through pipes to the cooling coils in each of the fans. When the water exits the cooling coil, it is much warmer and it is piped back to the chiller to be re-cooled. There is also a separate condenser water system which removes heat from the chiller units at a cooling tower which is located outdoors (usually on the roof). This heated condenser water can be a good environment for the growth of Legionella pneumophila bacteria, which can cause Legionnaire's disease. In the summer time ,the outside air is often cooled from 80 ° F to a supply temperature of 60° F. The cooling of the air causes water to condense inside the fan unit on the cooling coil. The same thing happens on your window air conditioner except the water drips from the unit to the outside. In the office air handler or fan unit, this water is collected in a drip pan beneath the cooling coil and drained away through a floor drain. If water does not drain properly from the cooling coil, slime will build up. This slime contains high amounts of bacteria and molds which can be released into the ventilation system. HEATING During the winter months, the cooling system is shut down and the heating system is turned on. The building boiler is used to produce steam or hot water which is pumped to the heating coil located in each of the fan units. The steam heats the cold outside air to a supply temperature of 75 F. A thermostat in the supply air duct measures the temperature and this information is used to adjust the amount of steam entering the heating coil. Most buildings also have a perimeter heating system for outside offices which includes radiators or hot water baseboard heaters located along the outside walls of the building. In most air handling units the system must be set either on heating or cooling mode, but not on both. Probes inside the ducts measure the temperatures of the outside air, mixed air and supply air; the system controls use this information to adjust the outside and return air dampers in order to achieve a supply temperature close to that desired. The cooling or heating coils are intended to give a final adjustment to the supply air temperature. WHY DO HVAC SYSTEMS RECIRCULATE AIR ? It always takes energy to run a refrigeration unit or a boiler. Consequently, the more outside air a ventilation system takes in, the more steam or chilled water needed to either heat it or cool it. Under extreme weather conditions the coils may not be able to adequately adjust the air temperature and as a result the outside air dampers often run at a minimum opening. There is also a cost incentive to operate the outside air dampers in a close or minimum position in order to save energy and money. When the outside air dampers are at minimum or closed, air quality problems can soon develop. You can often visually determine whether the outside air dampers are opened or closed. If they are closed, it is usually indicative of an indoor air quality problem. VARIABLE VOLUME VENTILATION SYSTEMS Modern ventilation systems can vary the amounts of outside air supplied by the fan unit and also vary the amount of air delivered through a given supply air diffuser. This is called a variable air volume (VAV) system and is intended to save energy and maintain comfortable temperatures in many individual zones or areas. There are variable air volume dampers at the end of each supply duct branch which control the volume of air delivered to a zone. The VAV dampers are controlled by a thermostat located in the zone. During the summer when the thermostat calls for cooling the VAV dampers open air flow to the maximum level, and when heating is needed the VAV dampers close. Indoor air quality problems occur when the VAV dampers close so that no or insufficient air is provided to the zone. The return and supply air dampers work in concert with the VAV controls in order to vary the volume of supply air to the ventilation system at any given time. The VAV systems are all controlled by computers. There are other types of ventilation systems that are variations on the above design. These ventilation systems play an important role in maintaining good indoor air quality in an office building. It is extremely important that people investigating indoor air quality problems have an understanding of the design and operation of the ventilation system. FILTERS The outside and return air has dust in it which must be removed before the air goes through the coils. If not, dust will accumulate in the coils and clog them. This causes a decrease in air flow and decreases the ability of the coil to heat or cool the air. Old filters can become clogged with dust also decreasing air flow. The dust caked on the filters or in the coils become a source of pollutants including bacteria and molds. Proper maintenance of the ventilation system requires replacement of filters on a regular basis and cleaning of the coils. There are different types of filters which have a wide range of efficiency at removing dust. High efficiency filters (those with a dust spot efficiency rating of 85% or higher) can remove pollen, mold spores, bacteria or other dusts which may cause problems for people. Medium efficiency filters remove most dust and have a dust spot rating between 30 to 40%. Low efficiency filters will only remove large dust particles and are only intended to protect the coils. They do not remove mold spores or pollen. HVAC systems should use medium efficiency filters as a minimum. For further information, contact your local union or the CWA District 1 NYS Health and Safety Project at (212) 509-6994. This fact sheet was written by Edward A. Olmstead, CIH. It is published by the CWA District 1 NYS Health and Safety Project with partial funding from New York State Department of Labor Hazard Abatement Board Contract #C007987. The opinions expressed are not necessarily those of the NYS Department of Labor. 1998. NYS Health and Safety Project CWA District 1 80 Pine Street, 37th floor New York, NY 10005 (212) 509-6994